PLACEMENT GUIDELINES

Depending upon obstacles such as furniture or partitions, the area of coverage 

may be less or more than the sensing distances shown in the coverage pattern. 

This must be considered when planning the number of sensors and their 

placement. It is also recommended to place the sensor 4 to 6 feet away from air 

supply ducts as rapid air currents or the differences in temperatures may cause 

false activations.
Mount the sensor to the ceiling. The CI-355 is designed for a ceiling height of 

about 8-12 feet. Mounting above or below this range will significantly affect the 

coverage patterns. Be aware that as you decrease the mounting height, you 

decrease the range and increase the sensitivity to smaller motions. Conversely, 

when you increase the height, you increase the range and decrease the sensitivity 

to smaller motions. At heights of more than 

12-14 feet, you may start to significantly 

reduce sensitivity. As a general rule, each 

occupant should be able to clearly view the 

sensor.
Often the best location to install a CI- 355 in 

a closed office is off-center. Avoid placing 

a sensor directly in line with an open door 

through which it has a clear view out, as the 

sensor may detect people walking by. 

Masking the PIR Lens: 

Opaque adhesive tape is supplied so that sections of 

the PIR lens can be masked. This restricts the sensor’s view and allows you to 

eliminate PIR coverage in unwanted areas such as hallways outside of the desired 

coverage area. Since masking removes bands of coverage, remember to take this 

into account when troubleshooting coverage problems. 

Optimizing Coverage:

 To get complete 

coverage in an open office area, install 

multiple sensors so that there is an 

overlap with each adjacent sensor’s 

coverage area. 
For open office areas with partitions it is 

best to place sensors over intersection of 

four workstations.
For large areas of coverage use multiple 

sensors.

CI-205

36'

36'

CI-205

12'

18'

Summary of Contents for CI-355

Page 1: ...1200W Ballast LED 347VAC 0 1500W Ballast LED Operating Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC 300FC Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 m...

Page 2: ...an turn lights off after only 3 minutes if no activity is detected after 30 seconds of an occupancy detection The CI 355 operates on 120VAC 230VAC 1 277VAC or 347VAC COVERAGE PATTERN The CI 355 provid...

Page 3: ...At heights of more than 12 14 feet you may start to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a CI...

Page 4: ...LLING SENSORS Single Sensor Single Load WARNING This application does not allow for Load to increase Load Switch Load Hot Neutral Neutral Ground Optional Hot Neutral Neutral Load Load Load Line Neutra...

Page 5: ...rough the conduit knockout 2 Connect the high voltage wires to the appropriate terminals on the sensor 3 Align the sensor in the J Box so that the mounting screw tabs on the box match the key holes on...

Page 6: ...using the Test Mode 20 minutes setting DIP switches 1 2 3 are OFF 2 Ensure that the Light Level is at default maximum See the Light Level Feature section of this document for instructions 3 Remain st...

Page 7: ...e to function throughout the duration of Test Mode When Test Mode period expires the Light Level functionality will resume even if the Dip Switches remain set to Test Mode Setting Light Level 1 Make s...

Page 8: ...Cover Disabling Light Level Pressing the pushbutton for 5 seconds or more resets the light to default maxi mum Press and hold the Light Level button over 5s the LED will be ON and then OFF showing 5s...

Page 9: ...t 30 seconds the selected time delay applies Sensitivity Switch 5 Minimum forces a reduced detection range for the PIR Maximum forces the sensitivity to the maximum coverage area This setting is const...

Page 10: ...is set to 100 DIP switch 5 set to OFF 5 If it still does not flash call 800 879 8585 for Technical Support LED flashes 1 Check all sensor wire connections Lights do not turn OFF automatically 1 The se...

Page 11: ...eck if Light Level is enabled If occupancy indicator LED blinks every few seconds sensor is using Light Level feature If Light Level functionality is not desired press and hold for 5 seconds to return...

Page 12: ...sensors are white WARRANTY INFORMATION WattStopper warranties its products to be free of defects in materials and workmanship for a period of five 5 years There are no obligations or liabilities on th...

Reviews: