DIP SWITCH SETTING
The CI-355 has 6 DIP switches under the cover.
Time Delay: Switches 1, 2, 3
The sensor will hold the lights
ON
as long as
occupancy is detected. The time delay countdown
starts when no motion is detected. After no motion is
detected for the length of the time delay, the sensor
will turn the lights
OFF
.
Walk Through: Switch 4
Walk-through mode turns the lights
OFF
three
minutes after the area is initially occupied, if no
motion is detected after the first 30 seconds. If
motion continues beyond the first 30 seconds, the
selected time delay applies.
Sensitivity: Switch 5
• Minimum forces a reduced detection range for the
PIR.
• Maximum forces the sensitivity to the maximum
coverage area. This setting is constantly updated.
Service: Switch 6
To override all sensor functions, set DIP switch 6 to
the
ON
position. The red LED will come on and stay
on for the duration of the override.
This bypasses the light level and occupancy detection control functions of the
sensor.
www.wattstopper.com
Switch#
5 minutes
10 minutes
15 minutes
20 minutes
25 minutes
30 minutes
30 seconds
1 2 3
Time Delay
Test Mode/20 min
5
Minimum
PIR Sensitivity
Maximum
6
Normal
Service
Service
= ON
= OFF
= Factory Setting
4
Disabled
Enabled
Walk-Through
Feature