LIGHT LEVEL FEATURE

 

The Light Level feature holds lights off upon initial occupancy if adequate ambient 

light exists. It will not turn the lights off if they are on. The default setting is for 

maximum, meaning that even the brightest ambient light will not hold the lights 

off. 

Notes on Functionality

• 

Avoid mounting the sensor close to lighting fixtures

• 

Adjust during daylight hours when ambient light in the area is at desired level.

• 

Light Level cannot be enabled while Test Mode is active. Either 

wait for Test Mode to expire or select any of the other Time 

Delay settings before enabling the Light Level feature.

• 

The red LED will flash periodically to indicate 

the sensor has Light Level enabled.

• 

Light Level settings are only saved in the event of a power loss. Disabling 

Light Level and then reenabling it will not return it to previous settings.

• 

If Test Mode is enabled after Light Level has been set, Light Level 

functionality will cease to function throughout the duration of Test 

Mode. When Test Mode period expires, the Light Level functionality 

will resume, even if the Dip Switches remain set to Test Mode.

Setting Light Level

1.   Make sure Test Mode is not active.
2.   Toggle the state of the sensor, by briefly pressing the Light Level button, to 

include or exclude the lighting load from the light level calibration. Open the 

Front Cover and locate the LIght Level pusbbutton. See Sensor Adjustment.

3.    Press and hold the Light Level button between 2s and 5s. The red LED will 

be ON showing 2s is reached and then be OFF showing 5s has passed*. The 

sensor enters setup mode, as indicated by the rapidly flashing LED. The 

LED will flash throughout the setup process. Occupancy indications from 

the LED is disabled during setup.

4.    Move away from the sensor to avoid interference with light level detection. 

The sensor measures the light level for a 10 second period, then averages 

the readings and automatically sets the level that will be used as the new 

setting. The sensor will hold lights off when the ambient light exceeds this 

setting.

Visit our website for FAQs: www.wattstopper.com

Summary of Contents for CI-355

Page 1: ...1200W Ballast LED 347VAC 0 1500W Ballast LED Operating Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC 300FC Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 m...

Page 2: ...an turn lights off after only 3 minutes if no activity is detected after 30 seconds of an occupancy detection The CI 355 operates on 120VAC 230VAC 1 277VAC or 347VAC COVERAGE PATTERN The CI 355 provid...

Page 3: ...At heights of more than 12 14 feet you may start to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a CI...

Page 4: ...LLING SENSORS Single Sensor Single Load WARNING This application does not allow for Load to increase Load Switch Load Hot Neutral Neutral Ground Optional Hot Neutral Neutral Load Load Load Line Neutra...

Page 5: ...rough the conduit knockout 2 Connect the high voltage wires to the appropriate terminals on the sensor 3 Align the sensor in the J Box so that the mounting screw tabs on the box match the key holes on...

Page 6: ...using the Test Mode 20 minutes setting DIP switches 1 2 3 are OFF 2 Ensure that the Light Level is at default maximum See the Light Level Feature section of this document for instructions 3 Remain st...

Page 7: ...e to function throughout the duration of Test Mode When Test Mode period expires the Light Level functionality will resume even if the Dip Switches remain set to Test Mode Setting Light Level 1 Make s...

Page 8: ...Cover Disabling Light Level Pressing the pushbutton for 5 seconds or more resets the light to default maxi mum Press and hold the Light Level button over 5s the LED will be ON and then OFF showing 5s...

Page 9: ...t 30 seconds the selected time delay applies Sensitivity Switch 5 Minimum forces a reduced detection range for the PIR Maximum forces the sensitivity to the maximum coverage area This setting is const...

Page 10: ...is set to 100 DIP switch 5 set to OFF 5 If it still does not flash call 800 879 8585 for Technical Support LED flashes 1 Check all sensor wire connections Lights do not turn OFF automatically 1 The se...

Page 11: ...eck if Light Level is enabled If occupancy indicator LED blinks every few seconds sensor is using Light Level feature If Light Level functionality is not desired press and hold for 5 seconds to return...

Page 12: ...sensors are white WARRANTY INFORMATION WattStopper warranties its products to be free of defects in materials and workmanship for a period of five 5 years There are no obligations or liabilities on th...

Reviews: