background image

CI-355 

v3

360° Passive Infrared • Line Voltage 

Occupancy Sensor

 

with Light Level feature

SPECIFICATIONS

Voltages  ............................................. 120//230/277/347VAC, 50/60Hz
Load Ratings
 @120VAC .........................................0-800W Ballast/Tungsten/LED
      @230VAC (Single Phase)...............................0-1200W Ballast/LED 

 @277VAC 

 ...................................................... 0-1200W Ballast/LED

      @347VAC ...................................................... 0-1500W Ballast/LED
Operating Temperature ................................ 32° to 131°F (0° to 55°C)
Light Level One-Step Adjustment ....................................10FC–300FC
Time Delay Adjustment ............................... 30 seconds to 30 minutes 

  Walk-Through Mode ..............3 minutes if no activity after 30 sec. 

  Test Mode .......................................... 5 sec. upon DIP switch reset
PIR Coverage 

  Model CI-355 ............................................................... up to 1200ft

2

 

  Model CI-355-1 .............................................................up to 500ft

2

      Sensitivity Adjustment ............................ High or Low (DIP switch)

Santa Clara, CA 95050

  

Installation Instructions

Summary of Contents for CI-355

Page 1: ...1200W Ballast LED 347VAC 0 1500W Ballast LED Operating Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC 300FC Time Delay Adjustment 30 seconds to 30 minutes Walk Through Mode 3 m...

Page 2: ...an turn lights off after only 3 minutes if no activity is detected after 30 seconds of an occupancy detection The CI 355 operates on 120VAC 230VAC 1 277VAC or 347VAC COVERAGE PATTERN The CI 355 provid...

Page 3: ...At heights of more than 12 14 feet you may start to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a CI...

Page 4: ...LLING SENSORS Single Sensor Single Load WARNING This application does not allow for Load to increase Load Switch Load Hot Neutral Neutral Ground Optional Hot Neutral Neutral Load Load Load Line Neutra...

Page 5: ...rough the conduit knockout 2 Connect the high voltage wires to the appropriate terminals on the sensor 3 Align the sensor in the J Box so that the mounting screw tabs on the box match the key holes on...

Page 6: ...using the Test Mode 20 minutes setting DIP switches 1 2 3 are OFF 2 Ensure that the Light Level is at default maximum See the Light Level Feature section of this document for instructions 3 Remain st...

Page 7: ...e to function throughout the duration of Test Mode When Test Mode period expires the Light Level functionality will resume even if the Dip Switches remain set to Test Mode Setting Light Level 1 Make s...

Page 8: ...Cover Disabling Light Level Pressing the pushbutton for 5 seconds or more resets the light to default maxi mum Press and hold the Light Level button over 5s the LED will be ON and then OFF showing 5s...

Page 9: ...t 30 seconds the selected time delay applies Sensitivity Switch 5 Minimum forces a reduced detection range for the PIR Maximum forces the sensitivity to the maximum coverage area This setting is const...

Page 10: ...is set to 100 DIP switch 5 set to OFF 5 If it still does not flash call 800 879 8585 for Technical Support LED flashes 1 Check all sensor wire connections Lights do not turn OFF automatically 1 The se...

Page 11: ...eck if Light Level is enabled If occupancy indicator LED blinks every few seconds sensor is using Light Level feature If Light Level functionality is not desired press and hold for 5 seconds to return...

Page 12: ...sensors are white WARRANTY INFORMATION WattStopper warranties its products to be free of defects in materials and workmanship for a period of five 5 years There are no obligations or liabilities on th...