background image

4

Common Blocks

 

The 368 has 2 common blocks for both the RTU inputs and the relay outputs. Each
common block has a terminal starting with 

Com (Eg. Com Sen or Com 1-2 ). Each

common block can be used for either two One Stage zones or one Two Stage zone.

One Stage Common Blocks   



If an RTU is connected to the lowest number in the common block, a One Stage common
block is created.

Example An RTU connected between the terminals 

Com Sen — RTU 1 is used to control

the output relay 

1, and an RTU connected between the terminals Com Sen —

RTU 2 is used to control the output relay 2.

Note If only one RTU is used, it must be placed on the lower number in the common

block. In the above example this would be 

Com Sen — RTU 1 controlling output

relay 

Com 1-2 — 1.

PID Zoning Logic

The 368 operation is based on a 15 minute cycle. During each cycle,
the control turns on the zone relay for a specific on time. This zone
on time is calculated based on the PID response of the zone during
the previous 15 minute period. If the zone needs more heat, the on
time is increased and if the zone needs less heat, the on time is
reduced. In order to prevent short cycling, the 368 ensures that the
zone relays remain on or off for at least 3 minutes.

Two Stage Common Blocks   



When a single RTU is connected to the highest terminal number in the common block,
a Two Stage common block is created. The single RTU therefore controls two output
relays: a 

Lo stage relay and a Hi stage relay.

Example An RTU connected between the terminals 

Com Sen — RTU 2 is used to

control the output relays 

1 and 2. Relay 1 is the Lo stage output relay and relay

2 is the Hi stage output relay.

PID Zoning logic

The temperature within each Two Stage zone is controlled by
varying the on time of the output relays over a 15 minute period.
During light loads, the 368 cycles the 

Lo stage relay on and off. As

the load increases, the 

Lo stage relay on time increases until it

reaches a maximum of 15 minutes. The 

Hi stage relay is then turned

on and its on time is increased as the load increases. When the
heating load decreases again, the on time of the 

Hi stage relay is

reduced until the 

Hi stage relay is turned off completely. The control

then starts to reduce the on time of the 

Lo stage relay.

Zone Control Load Staggering and Synchronization 

  

The 368 staggers the operation of the zones in order to achieve a steady load on the boiler while minimizing boiler running time and
preventing boiler short cycling. Multiple Zone Controls can be connected together to increase the number of zones. Each of the Zone
Controls synchronizes its zone operating cycles based on the 

Zo In input from the other Zone Controls. This results in a more stable

system flow rate and improved boiler operation.

Zone Control Operation with a tekmar House Control

The 368 can communicate with a tekmar House Control in order to
provide indoor temperature feedback, turn on the system pump and
operate the boiler. When multiple Zone Controls are used, each Zone
Control sequentially passes the information to the tekmar House
Control. This ensures that the heat requirements of all zones are
satisfied. When the 368 is requesting heat from the House Control, the
Heat Required light is turned on.

Fast Acting Zone Valves or Zone Pumps 

  

If the 

Thermal Motor DIP switch is set to Off, the 368 assumes that fast acting (electric

motor) zone valves or zone pumps are connected to the zone relays. The 

Heat Required

light is therefore turned on as soon as the first zone relay is turned on. One minute before
the last zone relay is turned off, the 368 purges the boiler by signaling to the House Control
to turn off the boiler and keep the system pump operating.

LR 58233

E150539

LR 58233

E150539

tekmar Zone Control

tekmar Zone Control

15 minute Cycle

Lo Stage

Lo Stage

Hi Stage

Hi Stage

Lo Stage

Hi Stage

Lo Stage

Off

Off

Off

On

On

On

On

On

H

C

R

Lo

Stage

Hi
Stage

M

M

Com

1-2

15

1

16

2

17

Com

Sen

5

6

RTU

1

RTU

2

7

Relay On Time

Relay On Time

Relay On Time

Less Heat

More Heat

15 minute Cycle

H

C

R

Zone 1

Zone 2

H

M

M

Com

1-2

15

1

16

2

17

Com

Sen

5

6

RTU

1

RTU

2

7

Fast acting
zone valve
or zone pump

Off

Thermal Motor

Summary of Contents for Tekmar Zone Control 368

Page 1: ...8 70 F 21 C 40 4 100 38 UnOccupied 5 6 7 LR 58223 NR T L C R Occupied Optimum Start Stop UnOccupied Timer Active 24 hr Timer 0 12 hrs 24 6 18 Dial the desired duration of the UnOccupied period Press s...

Page 2: ...eat can be supplied to the room on the coldest day of the year without requiring that the room be cold Derivative D In order to speed up the control s response to quick changes in the heating load der...

Page 3: ...ulationsonindoortemperatureonly Iftherearelargevariationsinoutdoor temperature this method cannot provide the same level of accuracy as when both indoor and outdoor sensors are used Optimum Start Stop...

Page 4: ...relay is then turned on and its on time is increased as the load increases When the heating load decreases again the on time of the Hi stage relay is reduced until the Hi stage relay is turned off co...

Page 5: ...cupied mode the UnOccupied light is turned on and the UnOccupied dial is used to set the desired temperature within the UnOccupied zones Note If the RTU dial for an UnOccupied zone is set below the Un...

Page 6: ...ng hardware and conduit fittings Before removing the knockouts check the wiring diagram and select those sections of the chamber with common voltages Do not allow the wiring to cross between sections...

Page 7: ...RTU 3 and RTU 4 If the common block is used for a Two Stage heating zone connect the RTU or Indoor Sensor to terminals Com Sen RTU 4 8 and 10 Output Connections System Pump Connect the live L side of...

Page 8: ...plied by the manufacturer If a zone pump or valve is connected to the terminals Com 1 2 2 15 and 17 follow a similar procedure as described above for the zone 1 relay If a zone pump or valve is connec...

Page 9: ...ic motor zone valves or zone pumps are used the DIP switch must be set to Off Testing the Control Functions STEP SEVEN OPERATIONAL TEST OF CONTROL FUNCTIONS The Zone Control 368 has a test routine whi...

Page 10: ...g system is turned off during the final stages of the Occupied period Timer Active The timer is set to enter the UnOccupied mode every 24 hours at the time of day the Start button was pressed STEP EIG...

Page 11: ...m Start Stop UnOccupied Timer Active Power Heat Required Occupied Optimum Start Stop UnOccupied Timer Active RTU 1 Temperature sensor open Power Heat Required Occupied Optimum Start Stop UnOccupied Ti...

Page 12: ...cable environmental health or safety legislation No implied warranties shall extend beyond twenty four 24 months from the production date Some states or provinces do not allow limitations on how long...

Reviews: