background image

2

Control Strategy

ZONING OPERATION  

In a multiple zone heating system, the zones may have different internal heat gains, heat losses or different temperature settings. Each
zone must therefore have individual temperature control. For maximum comfort, the heat should be continuously supplied to the zone
at the same rate the zone is losing heat. The most accurate method of accomplishing this is by outdoor reset; however, it is not normally
economical to modulate the supply water temperature to every zone.

Outdoor reset can be combined with zoning for a more cost effective solution. Through
indoor sensors, a zone control can provide indoor temperature feedback to the outdoor
reset control. The outdoor reset control will then adjust the supply water temperature to
satisfy the zone with the highest water temperature requirement. Heat to the remaining
zones will be cycled on and off by the zone control using zone valves or pumps. Since the
heat is cycled on and off, accurate PID control logic should be provided to maintain a stable
indoor temperature.

PID Zoning Logic  



Proportional (P)

In order to prevent indoor temperature swings, the heat supplied to each zone must be
proportional to the heat required by the zone. Proportional control logic can be
accomplished by pulse width modulation (PWM). A typical PWM system has a fixed
operating cycle. During this operating cycle, the on time of the zone relay is varied
based on the difference between the desired zone temperature and the actual zone
temperature. As the zone temperature drops, the relay on time increases and as the
zone temperature rises, the relay on time decreases.

Integral (I)

Controls that are strictly proportional suffer from a problem of offset. The amount of heat
supplied to the zone depends on how far the space temperature is below the desired
setpoint. This implies that as the heating load increases, the average room temperature
droops. On the coldest day of the year, the most heat is required and therefore the room
temperature must be coldest.
In order to overcome this offset, integral control logic is used. Only digital controls can provide integral control logic due to the lengthy
response time of buildings. Integral control logic is based on time. The longer the room temperature is below the desired setpoint,
the more heat is supplied to the room. With integral control logic, full heat can be supplied to the room on the coldest day of the
year without requiring that the room be cold.

Derivative (D)

In order to speed up the control’s response to quick changes in the heating load, derivative control logic is required. However,
sudden room temperature changes, for example from an open door or window, should be ignored by an intelligent control.

P + I + D = PID

If proportional, integral and derivative (PID) control logic are combined, the control is more able to prevent excessive temperature
swings and provide a stable room temperature under all conditions. It not only takes into account how much the room temperature
has drooped, but also how long there has been a droop and how fast the temperature is changing.

Zone Load Staggering 



In a multiple zone system, there can be sudden load changes on the boiler and system
due to multiple zones turning on or off. These sudden load changes often lead to boiler
short cycling and unnecessary mechanical stresses. The operation of the system can be
improved by staggering the starting points of each zone relay within the operating cycle.
Staggering of the zones maintains a relatively constant system flow rate which improves
boiler operation. Controlled staggering can also minimize boiler running time and improve
system efficiency when only a few zones are needed for short periods.

Zone Post Purge

 

Before the last zone is turned off in a heating cycle, the boiler is turned off but the zone continues to draw heat from the boiler. This
post purge of the boiler reduces stand-by losses and reduces overall energy consumption.

UNOCCUPIED (NIGHT SETBACK) 

During the night, or at times when people are not within the building, energy can be saved by lowering the building temperature for an
UnOccupied (Night Setback) period.

Due to the large thermal mass of buildings, it takes a long time for the indoor space temperature to significantly change whenever the
heating system is turned on or off. The building heat up or cool down time is further increased when high mass heating systems are
used (e.g. radiant floors). In most cases night setback cannot be used with these systems due to the long recovery time required in the
morning. A typical system is demonstrated in the diagram on page 3.

Zone 1

Zone 2

Zone 3

Zone 4

Post Purge

(Boiler off, Pump on)

On

On

On

On

On

70 

°

F

(21

°

C)

15 minutes

15 minutes

13 minutes

no heat

72 

°

F

(22

°

C)

68 

°

F

(20

°

C)

droop

70 

°

F

(22

°

C)

15 minutes

15 minutes

5 minutes

10 minutes

on

no heat

72 

°

F

(22

°

C)

68 

°

F

(20

°

C)

Heat

Source

90%

time on

85%

time on

100%

time on

M

M

M

Summary of Contents for Tekmar Zone Control 368

Page 1: ...8 70 F 21 C 40 4 100 38 UnOccupied 5 6 7 LR 58223 NR T L C R Occupied Optimum Start Stop UnOccupied Timer Active 24 hr Timer 0 12 hrs 24 6 18 Dial the desired duration of the UnOccupied period Press s...

Page 2: ...eat can be supplied to the room on the coldest day of the year without requiring that the room be cold Derivative D In order to speed up the control s response to quick changes in the heating load der...

Page 3: ...ulationsonindoortemperatureonly Iftherearelargevariationsinoutdoor temperature this method cannot provide the same level of accuracy as when both indoor and outdoor sensors are used Optimum Start Stop...

Page 4: ...relay is then turned on and its on time is increased as the load increases When the heating load decreases again the on time of the Hi stage relay is reduced until the Hi stage relay is turned off co...

Page 5: ...cupied mode the UnOccupied light is turned on and the UnOccupied dial is used to set the desired temperature within the UnOccupied zones Note If the RTU dial for an UnOccupied zone is set below the Un...

Page 6: ...ng hardware and conduit fittings Before removing the knockouts check the wiring diagram and select those sections of the chamber with common voltages Do not allow the wiring to cross between sections...

Page 7: ...RTU 3 and RTU 4 If the common block is used for a Two Stage heating zone connect the RTU or Indoor Sensor to terminals Com Sen RTU 4 8 and 10 Output Connections System Pump Connect the live L side of...

Page 8: ...plied by the manufacturer If a zone pump or valve is connected to the terminals Com 1 2 2 15 and 17 follow a similar procedure as described above for the zone 1 relay If a zone pump or valve is connec...

Page 9: ...ic motor zone valves or zone pumps are used the DIP switch must be set to Off Testing the Control Functions STEP SEVEN OPERATIONAL TEST OF CONTROL FUNCTIONS The Zone Control 368 has a test routine whi...

Page 10: ...g system is turned off during the final stages of the Occupied period Timer Active The timer is set to enter the UnOccupied mode every 24 hours at the time of day the Start button was pressed STEP EIG...

Page 11: ...m Start Stop UnOccupied Timer Active Power Heat Required Occupied Optimum Start Stop UnOccupied Timer Active RTU 1 Temperature sensor open Power Heat Required Occupied Optimum Start Stop UnOccupied Ti...

Page 12: ...cable environmental health or safety legislation No implied warranties shall extend beyond twenty four 24 months from the production date Some states or provinces do not allow limitations on how long...

Reviews: