background image

6

Exercising Procedure

The 368 first exercises the zone valves or pumps. If a zone valve or zone pump has not been operated in the past 3 days, the 368
turns on the zone relay for 10 seconds.

Note The zone relay exercising time is increased to 3 minutes if the DIP switch is set to 

Thermal Motor.

After the zone valves or pumps have been exercised, the 368 exercises the system pump. If the system pump has not operated
in the past 3 days, the 368 turns on the 

System Pmp relay for 10 seconds.

Once the exercising procedure is complete, the 368 returns to its normal operating sequence.

Installation

Caution

Improper installation and operation of this control could result in damage to the equipment and possibly even
personal injury. It is your responsibility to ensure that this control is safely installed according to all applicable codes
and standards. This electronic control is not intended for use as a primary limit control. Other controls that are
intended and certified as safety limits must be placed into the control circuit.

STEP ONE 

GETTING READY 

Check the contents of this package. If any of the contents listed are missing or damaged, please contact your wholesaler or tekmar sales
representative for assistance.

Type 368 includes:

• One Zone Control 368
• Data Brochures D 368, D 001
• Application Brochures A 368

Other information available:

• Essays

Note Carefully read the details of the Sequence of Operation sections in all applicable brochures to ensure that you have chosen the
proper control for your application.

STEP TWO 

MOUNTING THE BASE  

Remove the control from its base by pressing down on the release clip in the wiring chamber and sliding the control upwards. The base
is then mounted in accordance with the instructions in the Data Brochure D 001.

STEP THREE 

 ROUGH-IN WIRING 

All electrical wiring terminates in the control base wiring chamber. The base has standard 7/8" (22 mm) knockouts which accept common
wiring hardware and conduit fittings. Before removing the knockouts, check the wiring diagram and select those sections of the chamber
with common voltages. Do not allow the wiring to cross between sections as the wires will interfere with safety dividers which should
be installed at a later time.

Power must not be applied to any of the wires during the rough-in wiring stage.

• If a 10K Indoor Sensor is used for any zone, install the Indoor Sensor(s) according to the instructions in the Data Brochure 074 and

run the wiring back to the control.

• If a 10K RTU is used, install the RTU(s) according to the installation instructions provided in the Data Brochure D 054 and run the

wiring back to the control.

• If multiple Zone Controls are used, run two wires from one Zone Control to the next to create a chain.

• Run wires from the 120 V (ac) power to the control. 

Use a clean power source to ensure proper operation. Multi-strand 16 AWG

wire is recommended for all 120 V (ac) wiring due to its superior flexibility and ease of installation into the terminals.

• Run wires from the system pump and from each zone valve / pump to the control.

STEP FOUR 

 ELECTRICAL CONNECTIONS TO THE CONTROL 

The installer should test to confirm that no voltage is present at any of the wires. Push the control into the base and slide it down until
it snaps in firmly.

Powered Input Connections

   

120 V (ac) Power

Connect the 120 V (ac) power supply to terminals 

Power N — L (3 and 4).

Sensor and Unpowered Input Connections 

  

Do not apply power to these terminals as this will damage the control.

Zone Control Input and Output

Connect a wire between the 

Com Sen (13) terminals on each 368. Connect the Zo Out

(12) terminal on the first 368 to the 

Zo In  (14) terminal on the second 368. With several

Zone Controls, connect the 

Zo Out (12) terminal on the second 368 to the Zo In (14)

terminal on the third 368 and continue this process for each additional 368. The 

Zo Out

Com

Sen

UnO

Sw

5 6

RTU

1

12

11

13

Com

Sen

14

Zo

In

Zo

Out

RTU

2

7

RTU

3

9

RTU

4

10

8

Com

Sen

Com

Sen

UnO

Sw

5 6

RTU

1

12

11

13

Com

Sen

14

Zo

In

Zo

Out

RTU

2

7

RTU

3

9

RTU

4

10

8

Com

Sen

3

1 2

N

L

Pmp

4

Power

Pmp

System

Summary of Contents for Tekmar Zone Control 368

Page 1: ...8 70 F 21 C 40 4 100 38 UnOccupied 5 6 7 LR 58223 NR T L C R Occupied Optimum Start Stop UnOccupied Timer Active 24 hr Timer 0 12 hrs 24 6 18 Dial the desired duration of the UnOccupied period Press s...

Page 2: ...eat can be supplied to the room on the coldest day of the year without requiring that the room be cold Derivative D In order to speed up the control s response to quick changes in the heating load der...

Page 3: ...ulationsonindoortemperatureonly Iftherearelargevariationsinoutdoor temperature this method cannot provide the same level of accuracy as when both indoor and outdoor sensors are used Optimum Start Stop...

Page 4: ...relay is then turned on and its on time is increased as the load increases When the heating load decreases again the on time of the Hi stage relay is reduced until the Hi stage relay is turned off co...

Page 5: ...cupied mode the UnOccupied light is turned on and the UnOccupied dial is used to set the desired temperature within the UnOccupied zones Note If the RTU dial for an UnOccupied zone is set below the Un...

Page 6: ...ng hardware and conduit fittings Before removing the knockouts check the wiring diagram and select those sections of the chamber with common voltages Do not allow the wiring to cross between sections...

Page 7: ...RTU 3 and RTU 4 If the common block is used for a Two Stage heating zone connect the RTU or Indoor Sensor to terminals Com Sen RTU 4 8 and 10 Output Connections System Pump Connect the live L side of...

Page 8: ...plied by the manufacturer If a zone pump or valve is connected to the terminals Com 1 2 2 15 and 17 follow a similar procedure as described above for the zone 1 relay If a zone pump or valve is connec...

Page 9: ...ic motor zone valves or zone pumps are used the DIP switch must be set to Off Testing the Control Functions STEP SEVEN OPERATIONAL TEST OF CONTROL FUNCTIONS The Zone Control 368 has a test routine whi...

Page 10: ...g system is turned off during the final stages of the Occupied period Timer Active The timer is set to enter the UnOccupied mode every 24 hours at the time of day the Start button was pressed STEP EIG...

Page 11: ...m Start Stop UnOccupied Timer Active Power Heat Required Occupied Optimum Start Stop UnOccupied Timer Active RTU 1 Temperature sensor open Power Heat Required Occupied Optimum Start Stop UnOccupied Ti...

Page 12: ...cable environmental health or safety legislation No implied warranties shall extend beyond twenty four 24 months from the production date Some states or provinces do not allow limitations on how long...

Reviews: