background image

PWF Filter Systems 

 

 

 

 

   9

Figure 8: Drain Line Connection

9

INSTALLATION

STEP 5: Connect the Drain Line

If the drain line is a 5/8" flexible poly tube, slide the nut onto
the poly tube, then place the poly tube insert into the end of
the poly tube and tighten the nut on to the 3/4" drain line fit-
ting. The nut is only designed for use with flexible poly tube.
Use other nuts if attaching different materials. Run line to a
drain. Making sure you have a 1 1/2" airgap. You may use a
floor drain, standpipe or any open type drain (see Fig 10).
Do not use Vaseline, oils, or other unacceptable lubricants on
o-rings. A silicon lubricant may be used on the black o-ring.
Use a pliers or crescent wrench to tighten or unscrew the nut.
Do not use a pipe wrench to tighten or loosen nut. Do not use
pipe dope or other sealant on threads. Use Teflon tape on the
threads of the drain line control fitting when installing 3/4"
NPT or 1" straight fitting.

Figure 10: Also be sure drain line has an air gap.

Figure 11: Drain Line Connection

Figure 12: Operating Mode

Figure 13: Bypass Mode

Figure 14: Bypass Mode

Figure 9: Brine Draw Connection.

STEP 5: Start-up

Place the bypass valve in the “bypass” position or mode
(see figures 12-14 below.)

Open the main water supply valve.

Open a couple of cold water faucets that are to be conditioned
and let run until air is expelled and pipes are full.

Open the outlet valve of the bypass.

Close the bypass valve.

Press and hold the regen button on the keypad for 3 seconds.

This will put the valve in manual mode. Now press the Regen 
button twice.This will put the system in backwash. Slowly open the
inlet valve. (Open the valve a little at a time, pausing several times
to allow the unit to fill slowly and expel air.) When the tank has filled
and a steady flow to the drain is achieved, let the system run until
clear water can be seen coming from the drain line. When water is
clear press the regen button 4 times. This will take the valve back
to service position. Open several cold water and hot water faucets
and let run until hot water heater is full and cold water faucets have
expelled trapped air. Turn electrical power back on or re-light the
hot water heater. Now continue with control valve setup.

Figure 9: Operating Mode

Figure 10: Bypass Mode

Figure 11: Bypass Mode

Start Up

1.   Confirm that the bypass valve is in the bypass position (see im-

ages

 

9, 10 & 11 below)

2.   Place the bypass valve in the “bypass” position or mode (see 

figures 12-14 below.)

3.   Open the user supplied feed water valve. Check for leaks and 

repair as needed.

4.  Open the outlet valve of the bypass.
5.  Open a couple inside hot and cold faucets until all air has been 

purged from the plumbing system. then close the faucets.

6.  Initiate an Immediate Manual Regeneration by pressing and hold-

ing the “REGEN” button for 3 seconds. This will place the system 

into “Backwash” mode, unplug the system from its electrical 

outlet once it has cycled into the backwash position. This will stall 

the unit in the “Backwash” mode so all air can be purged from 

the tank.

7. Close the bypass valve.

 

8.  Adjust the user supplied feed water valve to 1/4 open and place 

the bypass valve into the “Service/Operating Mode” position.

9.  Air will come out of the drain line until the backwashing tank is 

completely purged of air. Then water will flow to drain. Allow 

water to flow to drain for 15 minutes or until the water to drain is 

clear of resin color throw.

10.  Plug the system back into the electrical outlet and manually cycle 

the control valve through the remaining regeneration steps by 

pressing the “Next” button until it arrives in the Service position.

11. Check for system for leaks and repair as needed.
12.  Installation is now complete and the system is ready for program-

ming.

Summary of Contents for PWFCAL15

Page 1: ...governing authorities for additional local requirements WARNING Need for Periodic Inspection Maintenance This product must be tested periodically in compliance with local codes but at least once per...

Page 2: ...6 15 5 3 16 X 11 X 62 PWFGAC2 Time Clock 12 X 52 2 30 8 15 7 5 17 X 13 X 60 PWFGAC3 Time Clock 14 X 65 3 40 11 15 10 18 X 14 X 74 PWFGAC4 Time Clock 16 X 65 4 60 14 15 11 20 X 17 X 74 MODEL NO VALVE...

Page 3: ...outlet must be grounded All electrical connections must be connected according to local codes Be certain the outlet is uninterrupted Install grounding strap on metal pipes The power adapter comes with...

Page 4: ...ipment If there is obvious damage to any equipment it should be noted on the carrier s Bill Of Lading Open and inspect the contents of all closed crates cartons etc and inspect for concealed damage Th...

Page 5: ...e oils or hydrocarbon based lubricants Use only 100 silicone lubricants Do not support the weight of the system on the control valve fittings plumbing or the bypass Do not allow this water conditionin...

Page 6: ...bracket towards the two latches The Service Instructions Figure 17 Figure 18 Figure 19 Figure 20 NOTICE NOTICE NOTICE Install a By Pass Always install a bypass either a 3 way valve system or the stan...

Page 7: ...es for an electrical ground metal only When finished with plumbing a ground wire should be connected to the copper pipes to complete the ground circuit Use two clamps and 4 copper for this Figure 5 Wh...

Page 8: ...ct to the control valve or the bypass valve using nuts that only require hand tighten ing Hand tighten nut connections between control valve and installation fittings control valve and bypass valve an...

Page 9: ...om the drain line When water is clear press the regen button 4 times This will take the valve back to service position Open several cold water and hot water faucets and let run until hot water heater...

Page 10: ...he Quick Programming Guide please see the detailed programming section of this manual NOTICE The electronics in the PWF control valve are used across a wide variety of control valves and applications...

Page 11: ...the hour the regeneration should occur by using the Up and Down arrow buttons an arrow points to PM after 12 00 noon Late night midnight is best this is the time when no water is liekly to be used Pr...

Page 12: ...7 Day option User Displays These procedures can be accessed in any order Details on each of the procedures are provided below and on the following pages When in operation normal user displays show th...

Page 13: ...points at Regen Hour Use UP or DOWN buttons to switch between the two choices If a differential switch is not installed the settings in this display are ignored NOTE A backwash will be initiated or s...

Page 14: ...rent day of the week by using the UP or DOWN buttons See chart at right for date codes Press SET HOUR to go to STEP 4I7 STEP 4I7 Sunday backwash To backwash on Sunday use the UP or DOWN button until t...

Page 15: ...ill always read 7 and a regeneration will never occur User Displays General Operation When the system is operating one of two displays will be shown Pressing UP or DOWN button will alter nate between...

Page 16: ...ests or a heavy laundry day To initiate a manual backwash at the preset delayed backwash time simultaneously press UP DOWN buttons together and release The arrow will point to the word Regen if a rege...

Page 17: ...PWF Filter Systems 17 NOTES...

Page 18: ......

Page 19: ......

Page 20: ...IMPLIED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND IN NO EVENT SHALL WATTS BE LIABLE IN CONTRACT TORT STRICT LIABILITY OR UNDER ANY...

Reviews: