Centurion Water Heater- Edge [ii]: Install-Operation-Service
SECTION 2: INSTALLATION
OMM-0153_A
• 8/25/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 33 of 131
Once system load is satisfied and all Client units have stopped firing, the WHM Manager opens
the Sequencing Valves of units specified in
Min Unit
settings in
Main Menu
→
Advanced
Setup
→
WHM Cascade
→
Cascade Comm
.
The implementation of WHM, and the installation and use of this valve, is optional. However,
when WHM is implemented
,
use of this valve is
strongly recommended
.
Installation consists of installing the Sequencing Valve in the hot water outlet pipe, and then
connecting it to the pre-wired connector on the shell harness, as described below.
NOTE:
The pre-programmed Sequencing Valve control is installed on Water Heaters that are
part of a Water Heater Management (WHM) group. Refer to Section SECTION 8: for
instructions.
WHM Sequencing Isolation Valve Installation:
1. Remove the Sequencing Isolation Valve from the shipping container.
2. Attach valve to the water outlet of the unit using the pipe union and nipple provided.
3. Ensure valve is positioned with the actuator enclosure position as shown in Figure 2-17:
Sequencing Valve Installation.
4. PVI recommends that another pipe nipple and flange be attached to the valve inlet prior to
connecting the water piping.
5. Tighten all pipe connections after the valve is properly positioned.
6. Connect the 5-pin Molex connector on the valve to the mating connector on the
CENTURION harness at the rear of the unit.
Figure 2-17: Sequencing Valve Installation
Sequencing
Isolation
Valve