47
Powers
TM
IntelliStation BAS Integration Manual
Vendor Name: Powers Control Systems Ltd.
Vendor ID: 834
Product Name: Intellistation Control Module
Product Model Number: 106901
Application Software Version: J1244L
BACnet Protocol Revision: 10
Product Description:
The Intellistation is a mixing control designed to deliver tempered water to plumbing fi xtures. The control uses
a Proportional Integral (PI) logic to accurately maintain a target temperature by mixing a high temperature
water source with a low temperature water source. This control also offers advanced features including
communication with a Building Automation System (BAS).
BACnet
®
Protocol Implementation Statement (PICS)
!
IntelliStation provides user-directed control and monitoring of water
distribution systems. It is the user’s responsibility to select and maintain
water temperatures and pressures that are safe and appropriate for the
water system users, guests and facility. IntelliStation’s Sanitization mode
is intended for use as part of a user-directed, controlled and supervised
protocol that has been safely and properly designed. It is recommended
to install IntelliStation
®
as part of a ASSE 1070 compliant water
distribution system, including point-of-use mixing valves. Always read
and follow User Guide & Instruction Manual and all product warnings
and labels, and comply with all governmental and safety requirements.
BACnet Standardized Device Profile (ANNEX L)
BACnet Application Specific Controller (B-ASC)
Supported BIBBs (Annex K)
Name
DS-RP-B
Data Sharing-ReadProperty-B
DS-RPM-B
Data Sharing-ReadPropertyMultiple-B
DS-WP-B
Data Sharing-WriteProperty-B
DM-DDB-B
Device Management-Dynamic Device Binding-B
DM-DOB-B
Device Management-Dynamic Object Binding-B
DM-DCC-B
Device Management-Device Communication Control-B
Note: Device communication control password is “Powers1017”.
Segmentation Capability
Supported
Able to transmit segmented messages
No
Able to receive segmented messages
No
Standard Object Types Supported
Creatable
Deletable
Analog Input
No
No
Analog Value
No
No
Binary Output
No
No
Data Link Layer
Supported
BACnet
®
IP (Annex J)
Yes
BACnet
®
MSTP
Yes
Device Address Binding
Supported
Static Device Address Binding
No
Network Security Options
Non-Secure Device
Character Set
Supported
ANSI X3.4
Yes