6
© Watts 2011
M-WWQP-HYDRO-1117
1.
Unplug the UV power supply and allow the lamp to cool for 30 minutes.
2.
Lift the UV lamp up and unplug the connector from the end of the lamp.
3.
Replace the lamp and plug in the connector. Avoid touching the sides of the lamp.
4.
Cover the lamp with the vinyl cap.
5.
Plug in the UV power supply.
Quartz Sleeve – Clean every 12 months and replace every 24 months
1.
Carefully remove the UV lamp. Avoid touching the sides of the lamp.
2.
Remove the quartz sleeve-retaining nut.
3.
Carefully remove the quartz sleeve.
4.
Clean the quartz sleeve with standard glass cleaner or replace it with a new one. Avoid
touching the sides of the quartz sleeve.
Troubleshooting:
Problem
Corrective Action
Low flow or high differential pressure
Replace filter cartridge
Short filter cartridge life
Install a prefilter upstream of the unit
UV lamp alarm
Replace the UV lamp
Replacement Parts
Part Number
Description
HSFSCART-PAC
0.2 micron pleated carbon cartridge
HSFSCART-ACP
5 micron pleated carbon cartridge
HSFSLAMP
Ultraviolet Lamp
HSFSQUARTS
Quartz Sleeve
WUVBALLAST6-12
UV Power Supply
HSFSUVOR
Quartz Sleeve O-Ring
HSFSUVNUT
UV Retaining Nut
PG15L25
Pressure Gauge 0 – 200 psi
HSFSCOUPLING-T
Inlet and Outlet Coupling Adapter with Gauge Port