Mounting instructions for accessories and spare parts:
Before working on the bar-switchcontrol,
isolate the unit from the voltage supply!
Spare part set 4:
Actuating shaft round initiator
• Disconnect the bar-switchcontrol and re-
move from the actuator.
• Press together the snap lock on the ac-
tuating shaft and pull out the shaft.
• Place spare actuating shaft in housing.
• Equip the spare cam with the actuating
devices, and push onto the spare actu-
ating shaft. Take care to observe, that
the actuating devices and their sides
are next to one another.
• Mount the bar-switchcontrol, set the ac-
tuating device, and remake the electrical
connection.
Spare part set 5:
Actuating shaft slot initiator
• Disconnect the bar-switchcontrol and re-
move from the actuator.
• Turn the actuating device with the ad-
justing tool, so that the actuating shaft
can be pulled out upwards, without colli-
ding with the initiator.
• Press together the snap lock on the ac-
tuating shaft and pull out the shaft.
• Place spare actuating shaft in housing.
• Equip the spare cam with the actuating
device, and push onto the spare actu-
ating shaft. Take care to observe, that
the actuating devices with their sides
are next to one another.
• Mount the bar-switchcontrol, set the ac-
tuating device, and remake the electrical
connection.
Spare part set 6:
Pressure compensating element
Replace blind plugs in the housing with a
reducer and screw the pressure compen-
sating element into the reducer.
Spare part set 7:
Solenoid valve switching
• Disconnect the bar-switchcontrol and re-
move from the actuator.
• Turn the actuating device with the ad-
justing tool, so that the actuating shaft
can be pulled out upwards, without colli-
ding with the initiator.
• Press together the snap lock on the actu-
ating shaft and pull out the shaft.
• Remove the black mounting plate.
• Disconnect the switch/initiator from the
terminal block.
•
Loosen the terminal block from the
mounting plate, whereby the mounting
on the underside is pushed temporarily
to one side.
• Push and click the 8x terminal block into
the mounting plate.
• Reconnect the switch/initiator according
to the circuit diagram in the inner side of
the housing.
•
Connect the descending cable to the
solenoid valve to the free terminal block
next to the switch/initiator cables.