background image

Operation

Installation

1. Prior to installation, flush line to remove debris.

2.  Install valve so the flow arrow matches flow through the line, and gauges to monitor valve inlet and outlet pressures. A Position  

Indicator can be installed to provide visual indication of valve position and operation without disassembly.

3. Install isolation valves upstream and downstream of the main valve.

Note: 

If using butterfly valves, ensure valve disc does not contact the main valve.

4. Provide adequate clearance for valve servicing and maintenance. Refer to valve servicing dimensions on next page.

5.  Avoid installing valves 6" and larger in the vertical position (main valve stem horizontal). Automatic Control Valves (ACVs) are  

designed for horizontal in-line installation, with the cover facing up (main valve stem vertical). Slow operation or premature stem and 

guide wear may occur if valve is not installed according to factory recommendations. Consult factory for detailed engineering review 

prior to ordering if valve is to be installed other than horizontally in-line.

6.  If valve is equipped with a pilot control system, extra precautions should be made during installation to protect the piping circuit from 

damage. Only remove the pilot control system from the valve if necessary. Tubing and fittings should be kept clean, and replaced 

exactly as removed. Consult appropriate hydraulic schematic to ensure proper re-assembly.

7. After installation, vent entrapped air from valve cover and pilot system by following instructions on Technical Bulletin.

The ACV Pressure Reducing Control Valve is designed to 
automati-cally reduce a fluctuating higher upstream pressure to 
a constant lower downstream pressure regardless of varying flow 
rates. It is controlled by a normally open, pressure reducing pilot 
designed to: 1) Open (allowing fluid out of the main valve cover 
chamber) when downstream pressure is below the adjustable 
setpoint, and 2) Close (allowing fluid to fill the main valve cover 
chamber) when downstream pressure is above the adjustable 
setpoint. A decrease in down-stream pressure causes the valve 
to modulate toward an open posi-tion, raising downstream pres-
sure. An increase in downstream pres-sure causes the valve to 
modulate toward a closed position, lowering downstream  
pressure.

Standard Components

1 — Main Valve (905GD – Single Chamber)

2 — Pressure Reducing Control

3 — Fixed Orifice

X — Isolation Cocks

910GD (Globe) Pressure Reducing Control Valve

2          IOM-A-ACV-910_610   2115 

EDP# 1917028 

© 2021 Watts

Summary of Contents for AMES 605AD

Page 1: ...ormation provided You are required to consult the local building and plumbing codes prior to installation If the information provided here is not consistent with local building or plumbing codes the l...

Page 2: ...ing installation to protect the piping circuit from damage Only remove the pilot control system from the valve if necessary Tubing and fittings should be kept clean and replaced exactly as removed Con...

Page 3: ...he valve Take proper precautions to protect your space from water damage STEP 1 Start with the upstream and downstream isolation valves in your system closed labeled 1 and 2 in Figure 1 respectively B...

Page 4: ...e valve number one in Figure 2 below Air is vented through the air bleed valve or loosened fitting Tighten the fitting when liquid begins to vent Repeat the process until no air is trapped in the syst...

Page 5: ...id increase in pressure possibly higher than the desired set point turn the adjustment screw IN clockwise decreasing the rate of opening STEP 7 Note If the main valve comes equipped with a closing spe...

Page 6: ...ve specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphr...

Page 7: ...embly by partially opening from full closed position Improperly configured opening speed control if equipped Adjust opening speed control to verify functionality adjust as required Standard setting fo...

Page 8: ...Remove cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may requi...

Page 9: ...e brush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are thr...

Page 10: ...Nuts in a crossing pattern to ensure even distribution Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integ...

Page 11: ...Stem Washer ASTM A276 304 Stainless Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 13...

Page 12: ...sts resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no c...

Reviews: