SmartPlate EV Installation, Operation and Maintenance Manual
CHAPTER 6
– SCHEDULED MAINTENANCE
OMM-0147_C
• SP-102 • 3/2/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
38
of
72
PLATE PACK LEAKAGE CHECKS
Instructions
3. If there is no evidence of leakage, reinstall the thermal jacket on the Plate Pack and return
the unit to service use.
6.3 OVER-TEMP SWITCH CHECK
Once every 3 months, check the Over-Temp switch located in the ECS II Control Box as
follows:
OVER-TEMP SWITCH CHECK Instructions
1. Follow the instructions in Section 4.2.3 to lower the Over-Temp setting to approximately
5°F below the present setpoint temperature shown in the lower display of the Temperature
Controller.
2. Verify that an over-temp alarm is generated and that the following events occur:
a) The 3-Way Control Valve closes.
b) The Over-Temp switch generates an audible alarm.
3. Following successful completion of the Over-Temp alarm check, return the Over-Temp
switch
setting to its original setting (20°F above the unit’s setpoint).
6.4 STRAINER INSPECTION AND CLEANING
Every 6 months, check and clean the Strainers in both the Boiler Water and Domestic Water
piping of the unit. Perform the following steps for each Strainer:
STRAINER INSPECTION AND CLEANING Instructions
1. Attach a hose to the blow-down valve at the base of the Strainer. Cycle the blow-down
valve open and closed 6 times.
2. If Step 1 was not sufficient to clean the Strainer, refer to Chapter 8:
Corrective
Maintenance
, Section 8.2.3:
Strainers
.
Figure 6.4. Strainer & Blow-Down Valve Locations
BOILER WATER
INLET STRAINER
DOMESTIC WATER
INLET STRAINER
WITH BLOW-DOWN
VALVE