GF-5050
Innovation Series & ReCon Water Heater
TAG-0043_0Q
Venting and Combustion Air Guide
Page
6
of
39
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, New York 10913
•
Phone: 800-526-0288
12/01/2016
OPTION 2: VP1738A
•
Van-Packer Company, Inc., Model CS Special Gas Vent
OPTION 3: Polypropylene
•
DuraVent, PolyPro Commercial.
NOTE
: Centrotherm provides the adapter when ordering
through them directly. However, when ordering through DuraVent, the customer must
purchase the required adapter separately. Refer to section 1.5 for adapter information
•
Centrotherm ECO Systems, InnoFlue Single Walk Commercial
OPTION 4: PVC/cPVC *
If needed, a PVC Vent Adapter is provided in the Spares Kit included with each
Innovation water heater.
* NOTE
PVC and cPVC venting are not allowed for ReCon water heaters.
Because Innovation and ReCon water heaters are Category II and IV appliances, they require special
attention to exhaust venting and combustion air details. The exhaust vent MUST be UL listed for use
with Category II and IV appliances.
Proper clearances to combustibles must be maintained per UL and vent manufacturer requirements.
The UL, National Fuel Gas Code (ANSI Z223.1/ NFPA54)
1
and CSA B149.1-10 guidelines are often
the basis for state and local codes. AERCO's recommendations follow the guidelines of these
agencies, unless more stringent codes govern the installation site. The venting and combustion air
systems must meet all applicable code requirements.
All Canada installations must comply with CSA B149.1 installation code.