Innovation Series & ReCon Water Heater
GF-5050
Venting and Combustion Air Guide
TAG-0043_0Q
12/01/2016
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, New York 10913
•
Phone: 800-526-0288
Page
23
of
39
NOTE
:
Vertical terminations shall extend at least 3 feet (0.9 m) above the highest
point where it passes through a roof of a building and at least 2 feet (0.6 m)
higher than any portion of the building within a horizontal distance of 10 feet
(3.1 m). Termination that extend more than 2 feet (0.6 m) above the roof must
be laterally supported
Figure 9: Determining Location of Vent Outlet
Vent terminations must be at least
3 feet (0.9 m) above and 10 feet
(3.1 m) away from any fresh-air
inlet.
Vent terminations must be at least 4
feet (1.2 m) horizontally from any
electric meter, gas meter or relief
equipment.
Vent terminations must be
at least 3 feet (0.9 m)
from inside corners.
Vent terminations must be
4 feet (1.2 m) from below
any doors, windows, or
gravity air intake.
Vent terminations must be at least 12”
(301 mm) above grade, and
consideration should be given to areas
where snow may accumulate.
Category II or IV must not terminate
over public walkways or over areas
where condensate or vapors could
create a nuisance or hazard.
VENT
VENT
VENT
VENT
UTILITY
EQUIPMENT