Ufly Controller and BCM for Modulex EXT
CHAPTER 8: TROUBLESHOOTING
OMM-0159_A
• 6/28/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
74
of
83
8.1.2 BMM (Burner Management Module) Fault Codes
The table below lists the fault codes and troubleshooting tips associated with the BMM.
CODE
DESCRIPTION
EFFECT
CORRECTION
RESET
BMM: 1
Overheat
thermostat
High Limit (STB)
Thermostat activated.
All burners turned OFF
and pump ON at
maximum speed.
Check flow sensor thermal
connection to boiler.
MANUAL - push
reset switch
when
temperature
goes below
limit.
BMM: 4
Ignition
failure
No flame detected at
burner start.
Burner control lockout. Check flame rod or combustion.
MANUAL - push
reset switch or
cycle power.
BMM: 5
Flame lost
Flame loss during run. Ignition retry.
Check combustion and wiring.
MANUAL - push
reset switch or
cycle power.
BMM: 6
Overheating
High outlet
temperature. Flow
sensor temperature >
203°F.
All burners turned OFF
and pump ON at
maximum speed.
Check flow sensor or system
pump
AUTOMATIC -
when Flow
sensor < 176°F.
BMM: 10
Internal
failure
Internal failure.
Ignition is inhibited.
Contact factory for new BMM.
MANUAL - cycle
the power.
BMM: 11
Unexpected
flame
Flame signal detected
before ignition.
Ignition is inhibited.
Disconnect flame rod wire from
BMM. If problem goes away,
change flame rod and/or wire. If
problem does not go away,
change BMM.
MANUAL - push
reset switch or
cycle power.
BMM: 12
CH flow
sensor
Flow sensor fault.
All burners turned OFF.
Check flow sensor and its
resistance using the
resistance/Temp table); check the
sensor connections.
AUTOMATIC
BMM: 14
CH return
sensor
Return sensor fault. -
NOT APPLICABLE
BMM: 15
Differential
temperature
Maximum Δ
-
temperature
protection.
Fault is detected if
Local FlowSensor
–
Return Sensor] >
[Param 483 + 50°F].
Note: Referred
parameter is BMM
Param. 483
All burners turned OFF
and Pump ON at
maximum speed.
Check the system installation.
AUTOMATIC -
Fault is cleared
when [Local
FlowSensor
–
Return Sensor]
< Param 483.
Note: Referred
parameter is
BMM Param.
483
BMM: 16
Frozen
Boiler pipe is frozen.
Flow sensor
temperature is 36°F or
less.
Ignition is inhibited.
Pump runs for 5 min at
max speed.
Carefully defrost boiler.
AUTOMATIC -
when flow
sensor is greater
than 41°F.