Ufly Controller and BCM for Modulex EXT
CHAPTER 7: BCM MODBUS AND ADDRESS ASSIGNMENTS
OMM-0159_A
• 6/28/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
68
of
83
Table 7-4: BCM Standard Holding Register Address Mapping
Modbus Data
Address
Menu Item
Units and Range
Default/(Comments)
TEST REGISTERS
1040
Test Mode Control
enum (0xA5/0x5A)
0xA5: Test mode release
0x5A: Test mode request
(Write Only)
This command is only
executed in Standby mode.
The other Write messages
are executed only in Test
mode.
1109
Pump Modulation
Output
0-10V
(Value x 10)
(Read/Write)
3100
Digital inputs status
[0, 1]
Flags (0 - 0xFFFF)
bit 0: Input1
bit 1: Input2
bit 2: Input3
bit 3: Input4
bit 4: Input5
bit 5: Input6
bit 6: Input7
bit 7: Input8
bit 8: Key1
bit 9: Key2
bit 10: SW1-1
bit 11: SW1-2
bit 12: SW1-4
bit 13: eBUS RX
bit 14: eBUS-1 RX
bit 15: not used
(Read Only)
3101
Digital outputs status
[0, 1]
Flags (0 - 0xFF)
bit 0: Relay1 [OFF, ON]
bit 1: Relay2 [OFF, ON]
bit 2: Relay3 [OFF, ON]
bit 3: Relay4 [OFF, ON]
bit 4: DL1 [OFF, ON]
bit 5: DL2 [OFF, ON]
bit 6: DL3 [OFF, ON]
bit 7: DL4 [OFF, ON]
(Read Only)