ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B
• 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
105
of
140
247
Units Active
SMD_BAS_IP_OpVal_[7]
✓
AV:107
Data Float
13
nvoOpVal_8
inc count (9)
Output (non-polled)
30107
247
Units Faulted
SMD_BAS_IP_OpVal_[8]
✓
AV:108
Data Float
14
nvoOpVal_9
inc count (9)
Output (non-polled)
30108
247
Master Addr
SMD_BAS_IP_OpVal_[9]
✓
AV:109
Data Float
15
nvoOpVal_10
inc count (9)
Output (non-polled)
30109
247
Header Temp
SMD_BAS_IP_OpVal_[10]
✓
AV:110
Data Float
16
nvoOpVal_11
inc count (9)
Output (non-polled)
30110
247
Outdoor Temp
SMD_BAS_IP_OpVal_[11]
✓
AV:111
Data Float
17
nvoOpVal_12
inc count (9)
Output (non-polled)
30111
247
Percent Output
SMD_BAS_IP_OpVal_[12]
✓
AV:112
Data Float
18
nvoOpVal_13
inc count (9)
Output (non-polled)
30112
247
Number of Units
Firing
SMD_BAS_IP_OpVal_[13]
✓
AV:113
Data Float
19
nvoOpVal_14
inc count (9)
Output (non-polled)
30113
247
Master Active
Setpoint
SMD_BAS_IP_OpVal_[14]
✓
AV:114
Data Float
20
nvoOpVal_15
inc count (9)
Output (non-polled)
30114
247
Next Turn-On
Percent
SMD_BAS_IP_OpVal_[15]
✓
AV:115
Data Float
21
nvoOpVal_16
inc count (9)
Output (non-polled)
30115
247
Header High Limit
SMD_BAS_IP_OpVal_[16]
✓
AV:116
Data Float
22
nvoOpVal_17
inc count (9)
Output (non-polled)
30116
247
Header Low Limit
SMD_BAS_IP_OpVal_[17]
✓
AV:117
Data Float
23
nvoOpVal_18
inc count (9)
Output (non-polled)
30117
247
Header Temp High
Limit
SMD_BAS_IP_OpVal_[18]
✓
AV:118
Data Float
24
nvoOpVal_19
inc count (9)
Output (non-polled)
30118
247
Header Setpoint
Mode
SMD_BAS_IP_OpVal_[19]
✓
AV:119
Data Float
25
nvoOpVal_20
inc count (9)
Output (non-polled)
30119
Write Master Operating Values
247
Setpt
SMD_BAS_IP_CtrlVal_[0]
AV:200
Data Float
26
nvoCtrlVal_1
inc count (9)
Input (non-polling)
40200
247
Setback Setpt
SMD_BAS_IP_CtrlVal_[1]
AV:201
Data Float
27
nvoCtrlVal_2
inc count (9)
Input (non-polling)
40201
247
Setback Start
SMD_BAS_IP_CtrlVal_[2]
AV:202
Data Float
28
nvoCtrlVal_3
inc count (9)
Input (non-polling)
40202
247
Setback End
SMD_BAS_IP_CtrlVal_[3]
AV:203
Data Float
29
nvoCtrlVal_4
inc count (9)
Input (non-polling)
40203
* NOTE:
Writing a setpoint to WHM or BST is a two-
step process. First write the setpoint to the “Write Setpoint” address. Next, write a “1” to the
“Write Control” address. This will cause the ProtoNode to send the setpoint to the master C-More. After the setpoint is sent, this address
value will change to “0” when read.