![background image](http://html.mh-extra.com/html/watts/64168/64168_user-manual_876893101.webp)
ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B
• 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
101
of
140
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME Lon SNVT Lon Direction
Modbus
Address
13
Outlet Temp
SMD_BAS_IP_HTR_13_[3]
✓
AV:1503
Data Float
289
nvoHTR_13_4 inc count (9)
Output (non-polled)
31503
13
FFWD Temp
SMD_BAS_IP_HTR_13_[4]
✓
AV:1504
Data Float
290
nvoHTR_13_5 inc count (9)
Output (non-polled)
31504
13
Inlet Temp
SMD_BAS_IP_HTR_13_[5]
✓
AV:1505
Data Float
291
nvoHTR_13_6 inc count (9)
Output (non-polled)
31505
13
Exhaust Temp
SMD_BAS_IP_HTR_13_[6]
✓
AV:1506
Data Float
292
nvoHTR_13_7 inc count (9)
Output (non-polled)
31506
13
Air Temp
SMD_BAS_IP_HTR_13_[7]
✓
AV:1507
Data Float
293
nvoHTR_13_8 inc count (9)
Output (non-polled)
31507
13
Flame Strength
SMD_BAS_IP_HTR_13_[8]
✓
AV:1508
Data Float
294
nvoHTR_13_9 inc count (9)
Output (non-polled)
31508
13
Fire Rate In
SMD_BAS_IP_HTR_13_[9]
✓
AV:1509
Data Float
295
nvoHTR_13_10 inc count (9)
Output (non-polled)
31509
13
Fire Rate Out
SMD_BAS_IP_HTR_13_[10]
✓
AV:1510
Data Float
296
nvoHTR_13_11 inc count (9)
Output (non-polled)
31510
13
Unit Type
SMD_BAS_IP_HTR_13_[11]
✓
AV:1511
Data Float
297
nvoHTR_13_12 inc count (9)
Output (non-polled)
31511
13
Unit Size
SMD_BAS_IP_HTR_13_[12]
✓
AV:1512
Data Float
298
nvoHTR_13_13 inc count (9)
Output (non-polled)
31512
13
Value State
SMD_BAS_IP_HTR_13_[13]
✓
AV:1513
Data Float
299
nvoHTR_13_14 inc count (9)
Output (non-polled)
31513
13
Net Remote Setpt
SMD_BAS_IP_HTR_13_[14]
✓
AV:1514
Data Float
300
nvoHTR_13_15 inc count (9)
Output (non-polled)
31514
13
Run Cycles Upper
SMD_BAS_IP_HTR_13_[15]
✓
AV:1515
Data Float
301
nvoHTR_13_16 inc count (9)
Output (non-polled)
31515
13
Run Cycles Lower
SMD_BAS_IP_HTR_13_[16]
✓
AV:1516
Data Float
302
nvoHTR_13_17 inc count (9)
Output (non-polled)
31516
13
Run Hours Upper
SMD_BAS_IP_HTR_13_[17]
✓
AV:1517
Data Float
303
nvoHTR_13_18 inc count (9)
Output (non-polled)
31517
13
Run Hours Lower
SMD_BAS_IP_HTR_13_[18]
✓
AV:1518
Data Float
304
nvoHTR_13_19
inc count (9)
Output (non-polled)
31518
13
Oxygen Level
SMD_BAS_IP_HTR_13_[19]
✓
AV:1519
Data Float
305
nvoHTR_13_20
inc count (9)
Output (non-polled)
31519
Blr Addr 14
14
Comm Address
SMD_BAS_IP_HTR_14_[0]
✓
AV:1600
Data Float
306
nvoHTR_14_1 inc count (9)
Output (non-polled)
31600
14
Unit Status
SMD_BAS_IP_HTR_14_[1]
✓
AV:1601
Data Float
307
nvoHTR_14_2 inc count (9)
Output (non-polled)
31601
14
Fault Code
SMD_BAS_IP_HTR_14_[2]
✓
AV:1602
Data Float
308
nvoHTR_14_3 inc count (9)
Output (non-polled)
31602
14
Outlet Temp
SMD_BAS_IP_HTR_14_[3]
✓
AV:1603
Data Float
309
nvoHTR_14_4 inc count (9)
Output (non-polled)
31603
14
FFWD Temp
SMD_BAS_IP_HTR_14_[4]
✓
AV:1604
Data Float
310
nvoHTR_14_5 inc count (9)
Output (non-polled)
31604
14
Inlet Temp
SMD_BAS_IP_HTR_14_[5]
✓
AV:1605
Data Float
311
nvoHTR_14_6 inc count (9)
Output (non-polled)
31605