ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B
• 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
96
of
140
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME Lon SNVT Lon Direction
Modbus
Address
7
Net Remote Setpt
SMD_BAS_IP_HTR_07_[14]
✓
AV:914
Data Float
180
nvoHTR_07_15 inc count (9)
Output (non-polled)
30914
7
Run Cycles Upper
SMD_BAS_IP_HTR_07_[15]
✓
AV:915
Data Float
181
nvoHTR_07_16 inc count (9)
Output (non-polled)
30915
7
Run Cycles Lower
SMD_BAS_IP_HTR_07_[16]
✓
AV:916
Data Float
182
nvoHTR_07_17 inc count (9)
Output (non-polled)
30916
7
Run Hours Upper
SMD_BAS_IP_HTR_07_[17]
✓
AV:917
Data Float
183
nvoHTR_07_18 inc count (9)
Output (non-polled)
30917
7
Run Hours Lower
SMD_BAS_IP_HTR_07_[18]
✓
AV:918
Data Float
184
nvoHTR_07_19 inc count (9)
Output (non-polled)
30918
7
Oxygen Level
SMD_BAS_IP_HTR_07_[19]
✓
AV:919
Data Float
185
nvoHTR_07_20 inc count (9)
Output (non-polled)
30919
Blr Addr 8
8
Comm Address
SMD_BAS_IP_HTR_08_[0]
✓
AV:1000
Data Float
186
nvoHTR_08_1 inc count (9)
Output (non-polled)
31000
8
Unit Status
SMD_BAS_IP_HTR_08_[1]
✓
AV:1001
Data Float
187
nvoHTR_08_2 inc count (9)
Output (non-polled)
31001
8
Fault Code
SMD_BAS_IP_HTR_08_[2]
✓
AV:1002
Data Float
188
nvoHTR_08_3 inc count (9)
Output (non-polled)
31002
8
Outlet Temp
SMD_BAS_IP_HTR_08_[3]
✓
AV:1003
Data Float
189
nvoHTR_08_4 inc count (9)
Output (non-polled)
31003
8
FFWD Temp
SMD_BAS_IP_HTR_08_[4]
✓
AV:1004
Data Float
190
nvoHTR_08_5 inc count (9)
Output (non-polled)
31004
8
Inlet Temp
SMD_BAS_IP_HTR_08_[5]
✓
AV:1005
Data Float
191
nvoHTR_08_6 inc count (9)
Output (non-polled)
31005
8
Exhaust Temp
SMD_BAS_IP_HTR_08_[6]
✓
AV:1006
Data Float
192
nvoHTR_08_7 inc count (9)
Output (non-polled)
31006
8
Air Temp
SMD_BAS_IP_HTR_08_[7]
✓
AV:1007
Data Float
193
nvoHTR_08_8 inc count (9)
Output (non-polled)
31007
8
Flame Strength
SMD_BAS_IP_HTR_08_[8]
✓
AV:1008
Data Float
194
nvoHTR_08_9 inc count (9)
Output (non-polled)
31008
8
Fire Rate In
SMD_BAS_IP_HTR_08_[9]
✓
AV:1009
Data Float
195
nvoHTR_08_10 inc count (9)
Output (non-polled)
31009
8
Fire Rate Out
SMD_BAS_IP_HTR_08_[10]
✓
AV:1010
Data Float
196
nvoHTR_08_11 inc count (9)
Output (non-polled)
31010
8
Unit Type
SMD_BAS_IP_HTR_08_[11]
✓
AV:1011
Data Float
197
nvoHTR_08_12 inc count (9)
Output (non-polled)
31011
8
Unit Size
SMD_BAS_IP_HTR_08_[12]
✓
AV:1012
Data Float
198
nvoHTR_08_13 inc count (9)
Output (non-polled)
31012
8
Value State
SMD_BAS_IP_HTR_08_[13]
✓
AV:1013
Data Float
199
nvoHTR_08_14 inc count (9)
Output (non-polled)
31013
8
Net Remote Setpt
SMD_BAS_IP_HTR_08_[14]
✓
AV:1014
Data Float
200
nvoHTR_08_15 inc count (9)
Output (non-polled)
31014
8
Run Cycles Upper
SMD_BAS_IP_HTR_08_[15]
✓
AV:1015
Data Float
201
nvoHTR_08_16 inc count (9)
Output (non-polled)
31015
8
Run Cycles Lower
SMD_BAS_IP_HTR_08_[16]
✓
AV:1016
Data Float
202
nvoHTR_08_17 inc count (9)
Output (non-polled)
31016