background image

6

Troubleshooting

PROBLEM 

CAUSE 

SOLUTION

1.  Long wait times for hot water?  

Troubleshooting Pump related issues

Pump does not have power

Check the power supply to the pump as well as the timer settings.

If there was a power outage, the timer does not reset and will require you to manually 

reset the timer.

Pump direction flow 

Check to ensure the pumps directional flow is correct.

Water supply angle stops

Verify the water supply angle stops are on and connected correctly to the Sensor valve.

Long Water Piping Network

Install a second Sensor Valve near or parallel the first one. (See Page 4)

2.  Long wait times for hot water?  

Troubleshooting Timer related issues

Timer Settings

Check to make sure the Timer Ring is set to the current time of day.

Manual Switch Setting Make sure the

Manual Switch is not set to the "OFF" position

Programming Tabs

Make sure there are not too many Programming Tabs pushed towards the center of 

the timer ring. This will indicated the timer is turned off.

AM/PM Settings

The timer is on a 24-Hour clock. Make sure the Timer is set for the correct 12 hour 

period "AM/PM"

3.  Long wait times for hot water? 

Troubleshooting Bypass related issues

Hot water does not reach a temperature above 

96°F (36°C)

Check the insulation on your hot water supply for damage.

If insulation is undamaged and sufficient, increasing the temperature of your heater/

boiler may be required.

Not enough time may have passed for the  

system to stabilize

This depends on a few different factors.

1. Piping Network Size

2. Hot water Tank

3. Water Usage

You can set your Hot Water Recirculating Pump to start 15 to 30 minutes earlier to 

compensate if necessary. The length of time will depend on the length of time you  

are having to wait.

Bypass Valve has failed

Follow these instructions to test the operation of your By-Pass Valve.

1. Verify that the pump is operational.

2. Check the Timer Switch and settings.

3.  Go to the sink where the Sensor Valve is installed. Close the cold water  

supply Angle Stop.

4. Open the cold water faucet.

5.  Wait for the water to slow down to a drip or no flow.  

This will take approximately 1 minute.

6.  If water does not slow to a drip or completely off, carefully check the  

temperature of the water. The temperature should be around around  

90°F (32°C) ± 4°

7. If the water temperature is more than 100°F, replace the valve.

No water flow

Verify the Sensor Valve is installed correctly. (See Page 4) The sensor valve can  

be installed vertically or horizontally, however, it must be installed facing the  

correct direction.

Hot water on one end of the hose but not  

the other

Verify that the sensor valve is installed at the faucet with the greatest piping distance 

from the hot water heater. Uninstall the sensor valve and reinstall at the sink that is 

taking longer than normal. If this does not resolve the issue, you may also have a 

branched line in your home which will require a second valve to be installed on the 

other end of the home.

Uninsulated piping or long runs of piping on 

concrete foundation.

You may require adding an additional valve or installing valves in parallel to increase 

the flow rate and reduce temperature drop. (See Page 4)

Summary of Contents for 500800

Page 1: ...ith installation Failure to read and follow attached instructions or operating parameters may lead to the product s failure and possible damage to property Refer to enclosed warranty for operating par...

Page 2: ...erature 140 F 60 C N A Step A Close the supply water valve to the water heater located in most cases above the water heater on the cold water inlet to the hot water heater STEP 1 Picture 2 ELECTRICAL...

Page 3: ...eat for the remaining flex hose to the cold water stop valve See Picture 5 Step E Open the hot water stop valve and proceed to Step B of Step 2 1 Check Sensor Valve Operation See Page 4 STEP 2 Step B...

Page 4: ...nd attach to the Hot Water Out and Cold Water Out of the new Sensor Valve Step C 3 8 Installation Connect the 3 8 side of the new flex hoses to the adapters installed on the previously installed Senso...

Page 5: ...ed only for use with the specified WATTS INSTANT HOT WATER RECIRCULATING SYSTEM System should be installed indoors on hot water service systems The timer control is designed to turn the circulator on...

Page 6: ...erent factors 1 Piping Network Size 2 Hot water Tank 3 Water Usage You can set your Hot Water Recirculating Pump to start 15 to 30 minutes earlier to compensate if necessary The length of time will de...

Page 7: ...around around 90 F 32 C 4 7 If the water temperature is more than 100 F replace the valve Incorrect Sensor Valve Installation See page 4 Water temperature from water heater boiler If the water is not...

Page 8: ...es to replace the equipment may replace it with reconditioned equipment Parts used in repairing or replacing the equipment will be warranted for 90 days from the date the equipment is returned to you...

Reviews: