background image

5

Ball Type Test Valves

Follow the requirements of each test when performed to ensure 

successful installation, operation, and maintenance of the 

backflow preventer.

Test No.1

Purpose:

 To test check valve No. 2 for tightness against 

reverse flow.

Requirements:

 Valve must be tight against reverse flow under 

all pressure differentials. Slowly open the ‘high’ valve A and the 

‘vent’ valve C, and keep the ‘low’ valve B closed. Open test No. 

4. Indicated pressure differential is expected to decrease slightly. 

If pressure differential continues to decrease (until the vent 

opens) check valve No. 2 is reported as ‘leaking.’

Test No. 2

Purpose:

 To test shutoff No. 2 for tightness.

Requirements:

 After passing test No. 1, continue to test No. 2 

by closing test cock No. 2. The indicated pressure differential is 

expected to decrease slightly. If pressure differential continues 

to decrease (approaching ‘zero’), shutoff No. 2 is reported to be 

‘leaking.’

Test No. 3

Purpose:

 To test check valve No. 1 for tightness.

Requirements:

 Valve must be tight against reverse flow under 

all pressure differentials. Close ‘high’ valve A and open test cock 

No. 2. Close test cock No. 4. Disconnect vent hose at test cock 

No. 4. Open valves B and C, bleeding to atmosphere. Then 

closing valve B restores the system to a normal static condition. 

Observe the pressure differential gauge. If there is a decrease in 

the indicated value, check valve No. 1 is reported as ‘leaking.’

Test No. 4

Purpose: 

To test operation of pressure differential relief valve.

Requirements:

 The pressure differential relief valve must 

operate to maintain the ‘zone’ between the two check valves at 

least 2 psi less than the supply pressure. Close ‘vent’ valve C. 

Open ‘high’ valve A. Open the ‘low’ valve B very slowly until the 

differential gauge needle starts to drop. Hold the valve at this 

position and observe the gauge reading when the first discharge 

is noted from the relief valve. Record this as the opening 

differential pressure of the relief valve.

NOTICE

The differential gauge needle MUST drop slowly. Close test 
cocks No. 2 and No. 3. Use the ‘vent’ hose to relieve pressure 
from the test kit by opening valves A, B, and C. Remove all 
test equipment and open shutoff No. 2.

CAUTION

!

To prevent freezing, hold Test Kit vertically to drain differential 

gauge and hoses prior to placing in case.

Testing Reduced Pressure Zone Assemblies

(A)

(C)

High Hose

(Yellow)

Low Hose

(White or Red)

Vent Hose

(Blue)

Test Cock 

No. 1

Test Cock 

No. 2

Test Cock 

No. 3

Test Cock 

No. 4

(B)

Needle

Valve

Summary of Contents for 4000SS-FS Series

Page 1: ...the service intended Regular checking and cleaning of the product s internal components helps assure maximum life and proper product function WARNING WARNING The installation and maintenance of backfl...

Page 2: ...ater authorities must approve all installation configurations Allow sufficient clearance around the installed assembly to conduct testing servicing and inspection Allow a minimum of 12 from the flood...

Page 3: ...lapper so that the end of the check arm rests between the roller and the clapper See Figure 5B Thoroughly clean the seat area and clapper sealing surfaces of both checks Inspect seats clapper sealing...

Page 4: ...hragm with the cupped hand The trapped air in the dia phragm forces the diaphragm between the inside of the sleeve and the outside of the piston Ensure that the diaphragm is fully seated If diaphragm...

Page 5: ...nect vent hose at test cock No 4 Open valves B and C bleeding to atmosphere Then closing valve B restores the system to a normal static condition Observe the pressure differential gauge If there is a...

Page 6: ...ure Leak through diaphragm or around flange bolt holes of relief valve Service relief valve Pressure relief valve does not close See problem Pressure relief valve does not close Assembly discharges fr...

Page 7: ...not included Add on and Retrofit Sensor Connection Kits for Cellular Communication ORDERING CODE ADD ON RETROFIT KIT DESCRIPTION 88009420 FP BF CFS 21 2 10 Cellular Sensor Connection Kit Series 4000S...

Page 8: ...s resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no con...

Reviews: