Watlow EZ-ZONE
®
ST
•
43
•
Chapter 4 Setup Page
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[`o;tb]
[ o.tb]
Digital Output (5 or 6)
Time Base
Set the time base for
fixed-time-base control.
0.1 for Fast and Bi-Directional
outputs, 5.0 for Slow out-
puts] to 60
Instance 5
Map 1 Map 2
171
1064
Instance 6
Map 1 Map 2
184
1094
0x6A
(106)
5 to 6
3
86
6003
Inst. 5
1004
Inst. 6
1034
float
RWES
[`o;Lo]
[ o.Lo]
Digital Output (5 or 6)
Low Power Scale
The power output will
never be less than the
value specified and will
represent the value at
which output scaling
begins.
0.0 to 100.0
0.0
Instance 5
Map 1 Map 2
178
1076
Instance 6
Map 1 Map 2
191
1106
0x6A
(106)
5 to 6
9
87
6009
Inst. 5
1016
Inst. 6
1046
float
RWES
[`o;hi]
[ o.hi]
Digital Output (5 or 6)
High Power Scale
The power output will
never be greater than
the value specified and
will represent the value
at which output scaling
stops.
0.0 to 100.0
100.0
Instance 5
Map 1 Map 2
180
1078
Instance 6
Map 1 Map 2
193
1108
0x6A
(106)
5 to 6
0xA (10)
88
6010
Inst. 5
1018
Inst. 6
1048
float
RWES
[`leu]
[ LEv]
Digital Input (5 or 6)
Level
Select which action will
be interpreted as a true
state.
[high]
High (37)
[LoW]
Low (53)
High
Instance 5
Map 1 Map 2
264
1290
Instance 6
Map 1 Map 2
268
1310
0x6E
(110)
5 to 6
1
137
10001
Inst. 5
1400
Inst. 6
1420
uint
RW
[``Fn]
[ Fn]
Digital Input (5 or 6)
Action Function
Select the function that
will be triggered by a true
state.
[none]
None (61)
[lmr]
Limit Reset (82)
[P;StS]
Profile Start/Stop
(208)
[ProF]
Start Profile (196)
[P;hoL]
Profile Hold/Resume
(207)
[P;diS]
Profile Disable (206)
[`t;dA]
TRU-TUNE+™ Dis-
able (219)
[`off]
Switch Loop Off (62)
[MAn]
Manual (54)
[tUnE]
Tune (98)
[idLE]
Idle Set Point (107)
[`F;AL]
Force Alarm to Occur
(218)
[`AoF]
Control Loops Off and
Alarms to Non-alarm State
(220)
[`SiL]
Silence Alarms (108)
[ALM]
Alarm (6)
[USr;r]
User Settings Restore
(227)
Instance 5
Map 1 Map 2
266
1294
Instance 6
Map 1 Map 2
270
1314
0x6E
(110)
5 to 6
3
138
10003
Inst. 5
1404
Inst. 6
1424
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EE-
PROM
S:
User
Set