Watlow EZ-ZONE
®
ST
•
55
•
Chapter 5 Profile Page
Profile Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index Par ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[S;typ]
[S.typ]
Step (1 to 40)
Step Type
Select a step type.
Time or rate depending
on setting of profile type
found on the Setup Page in
the the Global menu.
[UStP]
Unused Step (50)
[``ti]
Time (143)
[`End]
End
[``JL]
Jump Loop (116)
[w;bo]
Wait For Both (210)
[w;pr]
Wait For Process
(209)
[`w;E]
Wait For Event
(144)
[SoAH]
Soak (87)
[rAtE]
Rate (81)
Unused
Instance 1
Map 1 Map 2
500
4000
[Map1 Offset
+ 20]
[Map2 Offset
+ 100]
0x79
(121)
1 to (40)
1
- - - -
21001
Inst. 1
2870
Offset
+80
uint
RWE
[t;SP1]
[t.SP1]
Step (1 to 40)
Target Set Point Loop 1
Set the set point for this
loop.
-1,999.000 to 9,999.000 ºF
or -1,128.000 to 5,537.000
ºC
0.0
Instance 1
Map 1 Map 2
501
4002
[Map1 Offset
+ 20]
[Map2 Offset
+ 100]
0x79
(121)
1 to (40)
2
- - - -
21002
Inst. 1
2872
Offset
+80
float
RWE
[hoUr]
[hoUr]
Step (1 to 40)
Hours
Select the hours (plus
Minutes and Seconds) for a
timed step.
0 to 99
0
Instance 1
Map 1 Map 2
503
4004
[Map1 Offset
+ 20]
[Map2 Offset
+ 100]
0x79
(121)
1 to (40)
3
- - - -
21003
Inst. 1
2874
Offset
+80
uint
RWE
[Min]
[Min]
Step (1 to 40)
Step Type Parameters
Minutes
Select the minutes (plus
Hours and Seconds) for a
timed step.
0 to 59
0
Instance 1
Map 1 Map 2
504
4006
[Map1 Offset
+ 20]
[Map2 Offset
+ 100]
0x79
(121)
1 to (40)
4
- - - -
21004
Inst. 1
2876
Offset
+80
uint
RWE
[~SEC]
[ SEC]
Step (1 to 40)
Seconds
Select the seconds (plus
Hours and Minutes) for a
timed step.
0 to 59
0
Instance 1
Map 1 Map 2
505
4008
[Map1 Offset
+ 20]
[Map2 Offset
+ 100]
0x79
(121)
1 to (40)
5
- - - -
21005
Inst. 1
2878
Offset
+80
uint
RWE
[rate]
[rAtE]
Step (1 to 40)
Rate
Select the rate for ramp-
ing in degrees or units per
minute.
0 to 9,999.000°F or units
per minute
0 to 5,555.000°C per min-
ute
0.0
Instance 1
Map 1 Map 2
506
4010
[Map1 Offset
+ 20]
[Map2 Offset
+ 100]
0x79
(121)
1 to (40)
6
- - - -
21006
Inst. 1
2880
Offset
+80
float
RWE
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read
with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EE-
PROM
S: User
Set