Watlow EZ-ZONE
®
ST
•
53
•
Chapter 4 Setup Page
Setup Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro DP
Index
Par
ID
RUI/
GTW
Mod-
bus
Data
Type
&
Read/
Write
[CoM]
[`SEt]
Communications Menu
[Ad;M]
[Ad.M]
Communications (1)
Address Modbus
Set the network address
of this controller. Each de-
vice on the network must
have a unique address.
1 to 247
1
Instance 1
Map 1 Map 2
313
2052
0x96 (150)
1
2
- - - -
17007
Inst. 1
2320
uint
RWE
[bAUd]
[bAUd]
Communications
Baud Rate
Set the speed of this con-
troller's communications
to match the speed of the
serial network.
9,600 (188)
19,200 (189)
38,400 (190)
9,600
Instance 1
Map 1 Map 2
314
2054
0x96 (150)
1
3
- - - -
17002
Inst. 1
2322
uint
RWE
[`PAr]
[ PAr]
Communications
Parity
Set the parity of this con-
troller to match the parity
of the serial network.
[none]
None (61)
[EuEn]
Even (191)
[`odd]
Odd (192)
None
Instance 1
Map 1 Map 2
315
2056
0x96 (150)
1
4
- - - -
17003
Inst. 1
2324
uint
RWE
[M;hL]
[M.hL]
Communications
Modbus Word Order
Select the word order of
the two 16-bit words in
the floating-point values.
[hiLo]
Word High Low (1330)
[Lohi]
Word Low High (1331)
Low High
Instance 1
Map 1 Map 2
- - - - 2058
0x96 (150)
1
5
- - - -
17043 - - - - uint
RWE
[`C_F]
[ C_F]
Communications
Display Units
Select which scale to use
for temperature.
[```F]
°F (30)
[```C]
°C (15)
°F
Instance 1
Map 1 Map 2
- - - - 2060
0x96 (150)
1
6
199
17050 - - - - uint
RWE
[Map]
[ Map]
Communications (1)
Data Map
If set to 1 the control will
use PM legacy mapping.
If set to 2 the control will
use new mapping to ac-
commodate new functions.
1 to 2
1
Instance 1
Map 1 Map 2
- - - - - - - -
0x96 (117)
1
0x3B (59)
- - - -
17059 - - - - uint
RWE
[`nU;S]
[ nV.S]
Communications (1)
Non-Volatile Save
If set to Yes all values
written to the control will
be saved in EEPROM.
[`yes]
Yes (106)
[``no]
No (59)
Yes
Instance 1
Map 1 Map 2
317
2064
0x96 (150)
1
8
198
17051
Inst. 1
2420
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E:
EE-
PROM
S:
User
Set