PM3/PM6 LEGACY™ Express PID Controller • 25 •
Setup Menu
Setup Menu (cont.)
Display
Parameter Name Description
[`A;si]
[ A.Si]
Alarm Silencing
Turn alarm silencing on to allow the
user to disable the output tied (config-
ured) to this alarm
Appears if: When alarm type is set to
process or deviation alarm
Range (Defaults are shown in bold)
[`oFF]
Off
[``on]
On
[A;dSP]
[A.dSP]
A
larm Display
Display an alarm message when an
alarm is active.
Appears if: When alarm type is set to
process or deviation alarm
Range (Defaults are shown in bold)
[`oFF]
Off
[``on]
On
[``rP]
[ rP]
Ramp Action
Select when the controller's set point
will ramp to the defined end set point.
Appears if: Always
Range (Defaults are shown in bold)
[`oFF]
Off
,
[`Str]
Startup
[StPt]
Set Point Change,
[both]
Both
[`r;rt]
[ r.rt]
Ramp Rate
Set the rate for the set point ramp. Set the
time units for the rate with the Ramp Scale
parameter.
Appears if: Ramp Action is set to
Startup, Set Point or Both
Range Range is 0.0 to 9,999 deg F, or
0.0 to 5.555 deg. C per hour. (Defaults
are shown in bold)
1.0°F degrees or units per hr.
[`s;lo]
[ S.Lo]
Scale Low Output 1
Set the scale low for process output in
electrical units. This value; in volts or mil-
liamps, will correspond to 0% PID power
output.
Appears if: Output 1 is a Process set to
heat or cool
Range (Defaults are shown in bold)
-100.0 to 100.0,
0.0
SET UP MENU (Continued)
To enter the Setup Menu push and hold the
up and down arrow keys for approximately 3
seconds. Once there, push the green advance
key to scroll through to the prompt of choice
and then use the up and down arrow keys to
change the range.
Setup Menu
‰
[`loC]
Lockout Menu
[`SEn]
Sensor Type
[`Lin]
Linearization
[`deC]
Decimal
[`C_F]
Display Units
[`r;lo]
Range Low
[`r;hi]
Range High
[`fn1]
Function Output 1
[`o;ty]
Output Type
[`fn2]
Function Output 2
[`h;ag]
Heat Algorithm
[`h;sC]
Hysteresis (Heat & Cool)
[`C;Ag]
Cool Algorithm
[`A;ty]
Alarm Type
[`A;hy]
Alarm Hysteresis
[`A;lg]
Alarm Logic
[`A;lA]
Alarm Latching
[`A;bl]
Alarm Blocking
[`A;si]
Alarm Silencing
[A;dsp]
Alarm Display
[``rp]
Ramp Action
[`r;rt]
Ramp Rate
[`s;lo]
Scale Low
[`s;hi]
Scale High
[o;hi1]
Power Scale High Output 1
[o;hi2]
Power Scale High Output 2
[`Ad;s]
Zone Address
[btth]
Bluetooth