PM3/PM6 LEGACY™ Express PID Controller • 22 •
Setup Menu
‰
[`loC]
Lockout Menu
[`SEn]
Sensor Type
[`Lin]
Linearization
[`deC]
Decimal
[`C_F]
Display Units
[`r;lo]
Range Low
[`r;hi]
Range High
[`fn1]
Function Output 1
[`o;ty]
Output Type
[`fn2]
Function Output 2
[`h;ag]
Heat Algorithm
[`h;sC]
Hysteresis (Heat & Cool)
[`C;Ag]
Cool Algorithm
[`A;ty]
Alarm Type
[`A;hy]
Alarm Hysteresis
[`A;lg]
Alarm Logic
[`A;lA]
Alarm Latching
[`A;bl]
Alarm Blocking
[`A;si]
Alarm Silencing
[A;dsp]
Alarm Display
[``rp]
Ramp Action
[`r;rt]
Ramp Rate
[`s;lo]
Scale Low
[`s;hi]
Scale High
[o;hi1]
Power Scale High Output 1
[o;hi2]
Power Scale High Output 2
[`Ad;s]
Zone Address
[btth]
Bluetooth
Setup Menu
SET UP MENU
(Continued)
To enter the Setup Menu, push and hold the
up and down arrow keys for approximately
3 seconds. Push the green advance key to
scroll through to the prompt of choice. Use
the up and down arrow keys to change the
range.
Setup Menu (cont.)
Display
Parameter Name Description
[`dEC]
[ dEC]
Decimal
Set the precision of the displayed value.
Appears if: Always
Range (Defaults are shown in bold)
[```0]
Whole
,
[``0;0]
Tenths,
[`0;00]
Hundredths
[`C_F]
[ C_F]
Display Units
Select which units will be displayed.
Appears if: Always
Range (Defaults are shown in bold)
[```F]
°F
[```C]
°C
[r;Lo]
[ r.Lo]
Range Low
For process signals, this value scales the units
to minimum electrical units (0 volts or 4 mA). For
TC, RTD or Thermistor, this value is the param-
eter for setting the minimum allowable setpoint .
Appears if: Always
Range (Defaults are shown in bold)
-1,999.000 to 9,999.000
0.0
[r;hi]
[ r.hi]
Range High
For process signals, this value scales theunits to
maximum electrical units (10 volts or 20 mA). For
TC, RTD or Thermistor, this value is the param-
eter for setting the maximum allowable setpoint .
Appears if: Always
Range (Defaults are shown in bold)
-1,999.000 to 9,999.000
[`fn1]
[ fn1]
Function of Output 1
Select which function will drive this output.
Appears if: If output 1 is ordered
Range (Defaults are shown in bold)
[`oFF]
Off,
[CooL]
Cool,
[hEAt]
Heat,
[ALM]
Alarm
[`o;ty]
[ o.ty]
Output Type
Select whether the process output will oper-
ate in volts or milliamps.
Appears if: A process output
(PM _ C _ F _-_ AAA_ _ _)
Range (Defaults are shown in bold)
[uoLt]
Volts
[`MA]
Milliamps