PM3/PM6 LEGACY™ Express PID Controller • 12 •
Install and Wire
Power
power
power
98
99
CF
CD
CE
Slot C
•
47 to 63 Hz
• 10VA maximum power consumption (PM3 and PM6)
Low Power
• 12 to 40V
(dc)
• 20 to 28V
(ac) Semi Sig F47
High Power
• 85 to 264V
(ac)
•100 to 240V
(ac) Semi Sig F47
Note:
In the graphics below notice that the Slot A connector does not show labeling for the outputs.
Labeling for Slot A outputs is based on the controller part number.
C
A
T1 S1 R1
Output 1
Output 2
CF CD CE
98 99
PM3
C
A
Output
2
Output
1
B
98
99
CF
CD
CE
T1
S1
R1
PM6
Ó
Warning:
Use National Electric (NEC) or other
country-specific standard wiring and safety
practices when wiring and connecting this
controller to a power source and to electri-
cal sensors or peripheral devices. Failure to
do so may result in damage to equipment
and property, and/or injury or loss of life.
Note:
Maximum wire size termination and torque
rating:
• 0.0507 to 3.30 mm
2
(30 to 12 AWG)
single-
wire termination or two 1.31
mm
2
(16 AWG)
• 0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be labeled differently,
depending on the model number.
Note:
To prevent damage to the controller, do not
connect wires to unused terminals.
Note:
Maintain electrical isolation between analog in-
put 1 and switched dc/open collector outputs.