Tuning and Control
8LS User’s Guide 79
Distributed Zero Crossing (DZC)
DZC output is essentially a Time Proportioning output. However, for
each AC line cycle the controller decides whether the power should be
On or Off. There is no Cycle Time since the decision is made for each
line cycle. Since the time period for 60 Hz power is 16.6 ms, the
switching interval is very short and the power is applied uniformly.
Switching is done only at the zero crossing of the AC line, which helps
reduce electrical “noise”.
DZC output is primarily used for very fast acting electrical heating loads
using Solid State Relays (SSRs). For instance, the open air heater coil is
an example of a fast acting load. Do not use DZC output for
electromechanical relays.
The combination of DZC output and a solid state relay can
inexpensively approach the effect of analog phase angle fired control,
and can increase heater life.
Output Digital Filter
The output filter digitally filters the PID control output signal. It has a
range of 0-255 levels, which gives a time constant of 0-127.5 seconds.
Use the output filter if you need to filter out erratic output swings due to
extremely sensitive input signals, like a turbine flow signal or an open
air thermocouple in a dry air gas oven.
The output filter can also enhance PID control. Some processes are very
sensitive and require a high PB, so normal control methods are
ineffective. You can use a smaller PB- and get better control- if you use
the digital filter to reduce the high and low process output swings.
You can also use the filter to reduce output noise when a large derivative
is necessary, or to make badly tuned PID loops and poorly designed
processes behave properly.
Reverse and Direct Action
Reverse action is an output control action in which an increase in the
process variable causes a decrease in the output. Direct action is an
output control action in which an increase in the process variable causes
an increase in the output. Heating applications normally use reverse
action and cooling applications usually use direct action.
Summary of Contents for 8LS
Page 8: ...vi 8LS User s Guide...
Page 12: ...4 8LS User s Guide Overview...
Page 91: ...Tuning and Control 8LS User s Guide 83...
Page 92: ...84 8LS User s Guide Tuning and Control...
Page 96: ...88 8LS User s Guide Troubleshooting...
Page 128: ...120 8LS User s Guide Appendix B 8LS CP...
Page 139: ...Glossary 8LS User s Guide 131...
Page 140: ...Glossary 132 8LS User s Guide...