56 8LS User’s Guide
Setup
Linear Scaling Menus
NOTE
The next four menus appear only for Linear or
Pulse loops.
For all inputs automatic scaling is provided. To set the scaling enter a
high process variable in engineering units and a corresponding high
reading. Then enter a low process variable in engineering units and a
corresponding reading. Using points as near as possible to zero and full
scale is best. After these entries the process variable, the setpoint and
alarms will all be in engineering units.
High PV Display
Selectable range:
0-9999.
High RDG Display
Selectable range:
0-9999.
The high input reading is referenced to 60mV and is calculated using
this equation:
Low PV Display
Selectable range:
0-9999.
1
2
3
4
5
6
7
8
LOOP
PROCESS
UNITS
ALARM
SETPOINT
STATUS OUTPUT%
1 HI PV
? 1000
1
2
3
4
5
6
7
8
LOOP
PROCESS
UNITS
ALARM
SETPOINT
STATUS OUTPUT%
1 HI RDG
? 1000
HIGH RDG = (1000)
(Sensor output @ High PV)
60 mV
*
1
2
3
4
5
6
7
8
LOOP
PROCESS
UNITS
ALARM
SETPOINT
STATUS OUTPUT%
1 LO PV
? 0
Summary of Contents for 8LS
Page 8: ...vi 8LS User s Guide...
Page 12: ...4 8LS User s Guide Overview...
Page 91: ...Tuning and Control 8LS User s Guide 83...
Page 92: ...84 8LS User s Guide Tuning and Control...
Page 96: ...88 8LS User s Guide Troubleshooting...
Page 128: ...120 8LS User s Guide Appendix B 8LS CP...
Page 139: ...Glossary 8LS User s Guide 131...
Page 140: ...Glossary 132 8LS User s Guide...