44 8LS User’s Guide
Using the 8LS
If you have set the current loop to Manual control, this display appears
after you press
Enter
:
•
Press
Yes
to change the output power.
•
Press
Yes
or
No
to select a new power output level.
•
Press
Enter
to store your choice and go back to Single Loop display
Autotune
If you set the current loop control status to Tune and press Enter, the
controller automatically sets the loop to manual control, 100% output.
The autotune function then calculates the appropriate PID constants for
the loop and puts the loop in automatic control with the calculated PID
values.
The Autotune function will abort if:
•
Process variable goes over 75% of the setpoint.
•
PID constants were not calculated after 10 seconds (a failure of some
sort).
Ramp/Soak
Use the Ramp/Soak key only if the optional Ramp/soak package is
included in the controller. Information pertaining to programming and
operation of ramp and soak profiles is included in the Ramp/Soak
section.
1
2
3
4
5
6
7
8
LOOP
PROCESS
UNITS
ALARM
SETPOINT
STATUS OUTPUT%
6 SET MAN
OUT
? 0
H
T
Summary of Contents for 8LS
Page 8: ...vi 8LS User s Guide...
Page 12: ...4 8LS User s Guide Overview...
Page 91: ...Tuning and Control 8LS User s Guide 83...
Page 92: ...84 8LS User s Guide Tuning and Control...
Page 96: ...88 8LS User s Guide Troubleshooting...
Page 128: ...120 8LS User s Guide Appendix B 8LS CP...
Page 139: ...Glossary 8LS User s Guide 131...
Page 140: ...Glossary 132 8LS User s Guide...