![Watlow Controls 8LS User Manual Download Page 32](http://html2.mh-extra.com/html/watlow-controls/8ls/8ls_user-manual_3698325032.webp)
24 8LS User’s Guide
Installation
RTD Inputs
The standard industrial RTD is a 100 ohm Platinum three wire
assembly. We highly recommend using the 3-wire RTD. The
8LS will
be configured for the standard three wire RTD input.
Watlow Anafaze offers two standard DIN 385 Curve RTD input ranges,
as shown in the table below:
RTD Range resistors are Watlow Anafaze factory stock in .05%
tolerance.
Infrared Non-contact Temp. Sensors
The IRSM (infrared sensing module) is ideally suited for many infrared
non-contact temperature applications. It can be supplied by Watlow
Anafaze as a fully integrated system with the 8LS configured to provide
power for up to four IRSM modules and for direct connection of the
IRSM output. The following connections are required if the IRSM
internal ambient sensor is not used:
RTD
Type
Input
Range
Display
Resolution
RTD1
-100.0 to +300.0
°
C
-148.0 to +572.0
°
F
0.1
°
RTD2
-120.0 to 840.0
°
C
-184.0 to +1544.0
°
F
0.2
°
Range
RA
RB Alternate
RC
RTD1
80
Ω
22 K
Ω
22 K
Ω
RTD2
100
Ω
48 K
Ω
48 K
Ω
8LS
Signal
IRSM Wires
Pin
Color
Function
Analog In +
A
Orange
Signal Out (0-10 mAdc)
Analog In -
B
White
Signal Ground
Analog Gnd
K
Shield
+5 Vdc
E
Red
+5 Vdc supply
Logic Gnd
C
Black
Power Ground
Logic Gnd
J
Brown
No Peak Hold
No Connection
D
Green
+15 Vdc supply
No Connection
F
Blue
Ambient Sensor
No Connection
H
Yellow
Track and Hold
Summary of Contents for 8LS
Page 8: ...vi 8LS User s Guide...
Page 12: ...4 8LS User s Guide Overview...
Page 91: ...Tuning and Control 8LS User s Guide 83...
Page 92: ...84 8LS User s Guide Tuning and Control...
Page 96: ...88 8LS User s Guide Troubleshooting...
Page 128: ...120 8LS User s Guide Appendix B 8LS CP...
Page 139: ...Glossary 8LS User s Guide 131...
Page 140: ...Glossary 132 8LS User s Guide...