Maintenance Schedule
Perform the following procedures at the recommended intervals at a minimum. Environmental conditions affect the maintenance requirements. Inspect the
components frequently and create a maintenance schedule suitable to your application and environment. Replace wear components with equivalent components.
Use your serial number to gain access to the service parts lists associated with your system through the MyWaterous login at
Operation
Operation
Before
Before
Operation
Operation
Daily
Daily
Weekly
Weekly
12 Months
12 Months 24 Months
24 Months
Comment
Comment
Check the oil level.
X
X
Note that the oil level drops temporarily during
system operation.
Inspect the hoses and fittings.
X
X
Service operation.
X
Operate the system in air only mode once a week for
15 minutes.
Clean the wye strainer.
X
Clean the wye strainer after each use. This is
dependent on water quality.
Change the oil.
X
Replace the oil after first 30 hours of operation, then
yearly after that. Use ISO 68 low-foaming or anti-
foam hydraulic oil.
Change the oil filter.
X
Replace the oil filter when you replace the oil.
Change the air filter.
X
Replace the air filter more often in dusty or dirty
environments.
Inspect the air clutch and belt drive.
X
Inspect the equipment during routine maintenance.
Inspect the mounting hardware.
X
Change the separator filter.
X
Replace the separator filter after a sudden increase
in oil consumption.