background image

 

WL380

 Manual 

                                                                 Page 49 ‐ Revision:  2‐5‐2018 

12. No Water is Dispensing from One Side – Cold or Hot 

 
 

Possible Reason 

Solution 

Too much water pressure.   
 
Recommend 40 to 60 psi for 
the 

WL380

 

Water Treatment 

System

 to operate properly. 

Verify water pressure at the Inlet Bulkhead with a Pressure 
Regulator.   
 
Additional method of verification is to turn off water to unit and 
press the Dispense Button.  Does the Solenoid open without water 
pressure to the unit?  Listen for solenoid to activate, not the 
Dispense Button “click”. 
 
Adjust water pressure to 40‐60 psi. 

PCB  

Switch the hot and cold wires on PCB (red and blue connections). 
 
If water now dispenses from the opposite side, this is an indication 
that there is a PCB problem. 
 
Replace PCB 

Solenoid  

If both the Water Pressure and PCB have been ruled out, then it is 
the Solenoid. 
 
Replace Solenoid. 

See “

Green Flashing Light” 

Fault Code Section of this 
Manual

 

Indicates the Firewall UV system is not detecting adequate dose of 
UV to ensure safe water. 

 

 
13. Cold Water Dispenses from Faucet and Vent Outlet Simultaneously 

 
 

Possible Reason 

Solution 

Improper tubing attachment 
from the Cold Tank to Faucet 
or vice versa 

Verify tubing is connected properly from Cold Tank Outlets to 
correct Faucet attachments. 

Scale has formed inside Cold 
Tank outlet tube. 

Remove Cold Water Outlet Tube from Cold Tank to Faucet.  Pour 
some scale remover into Cold Tank. 

Expansion chamber in Cold 
Tank is not sealed properly. 

Replace Cold Tank. 

 
 
 
 

Summary of Contents for WL380

Page 1: ...ming out of Faucet Vent Hole 7 Low Flow of Water 8 Hot Water Drip out of Faucet 9 Dispenses Hot and Cold Water at the same time 10 No cold water available 11 Water does not dispense from unit 12 No Wa...

Page 2: ...Water Pressure to 40 60 psi Loose or bad connection on the Front Dispensing PCB or Solenoid Connector Check that they are connected properly and tightened Solenoid If both the Water Pressure and PCB...

Page 3: ...or Faulty Solenoid Replace Solenoid 4 Steady Drip Out of Faucet Possible Reason Solution Debris in Solenoid Inspect Solenoid for debris and clean out as needed 5 Hot Water or Steam Coming out of both...

Page 4: ...e Reason Solution Determine Flow of Water Rated Flow Rate is 1 89 Liters 0 5 gallons per minute Check flow rate by dispensing into a container to measure for one minute Measure the amount of water tha...

Page 5: ...ucet The Hot Tank Outlet Tube has a Restrictor in its base This ensures the reservoir is always full by allowing more water in than out There is a small hole in the side of the Hot Tank Outlet Tube th...

Page 6: ...oid Replace Solenoid as necessary 10 No Cold Water Available Possible Reason Solution Closed Water Supply Valve Open the Water Supply Valve Cold Water Solenoid Valve malfunction Inspect the valve comp...

Page 7: ...ch on I ON 15 Amp Fuse Blown Replace the 15 Amp Fuse as needed Water is present in the Bottom Tray causing the Leak Detection to trigger Remove the Top Cover and Front Panel Tip the unit slightly to d...

Page 8: ...w dispenses from the opposite side this is an indication that there is a PCB problem Replace PCB Solenoid If both the Water Pressure and PCB have been ruled out then it is the Solenoid Replace Solenoi...

Page 9: ...the tank to flush out the contaminant s 15 Dispense Buttons Stick Possible Reason Solution Dirt or Foreign material is filling the gap around the Dispense Buttons Inspect the Dispense Buttons and clea...

Page 10: ...cet The inlet solenoid controls flow into the tanks The tanks will depressurize once the dispense button is released the inlet solenoid closes A small amount of water will Run On through the faucet as...

Page 11: ...ot Tank is made from stainless steel Ensure descaling solution is compatible with stainless and always flush the unit completely Dispose in an environmentally safe manner Materials Needed Personal Pro...

Page 12: ...er above 52o C 125o F can cause severe burns or scalding Keep unauthorized people and children away from the unit to avoid accidental dispensing of hot water CAUTION MUST REPLACE HOT TANK 3 5 YEARS DE...

Reviews: