![WATERKOTTE EcoTouch DS 5027 Ai Planning And Installation Manual Download Page 27](http://html1.mh-extra.com/html/waterkotte/ecotouch-ds-5027-ai/ecotouch-ds-5027-ai_planning-and-installation-manual_3621920027.webp)
Installation and connection
2005/06/10
27 / 60
Copyright
2013 by: WATERKOTTE GmbH. Subject to changes.
Residual head. heating side (B0/W35):
Heat pump
EcoTouch
DS
5008.5Ai
DS
5010.5Ai
DS
5012.5Ai
DS
5014.5Ai
DS
5017.5Ai
DS
5020.5Ai
DS
5023.5Ai
DS
5027.5Ai
Flow rate
T 5K
m³/h
1.0
1.2
1.6
1.8
2.3
2.6
3.0
3.4
Pump (class A)
25/1-7
25/1-7
25/1-7
25/1-7
25/1-8
25/1-8
25/1-8
25/1-8
Residual head
T 5K
mWS
6.4
6.2
5.9
5.5
7.0
6.6
6.0
5.2
Residual head heat source side (B0/W35):
Heat pump
EcoTouch
DS
5008.5Ai
DS
5010.5Ai
DS
5012.5Ai
DS
5014.5Ai
DS
5017.5Ai
DS
5020.5Ai
DS
5023.5Ai
DS
5027.5Ai
Flow rate
T 4K
m³/h
1.1
1.3
1.7
1.9
2.5
2.8
3.2
3.7
Pump (class A)
25/1-7
25/1-7
25/1-7
25/1-7
25/1-8
25/1-8
25/1-8
25/1-8
Residual head
T 4K
mWS
6.4
6.1
5.7
5.2
6.7
6.2
5.3
4.5
Residual head heating side (W10//B8/4//W35):
Heat pump
EcoTouch
DS
5008.5Ai
DS
5010.5Ai
DS
5012.5Ai
DS
5014.5Ai
DS
5017.5Ai
DS
5020.5Ai
DS
5023.5Ai
DS
5027.5Ai
Flow rate
T 5K
m³/h
1.3
1.6
2.0
2.2
2.9
3.2
3.7
4.2
Pump (class A)
25/1-7
25/1-7
25/1-7
25/1-7
25/1-8
25/1-8
25/1-8
25/1-8
Residual head
T 5K
mWS
6.1
5.6
4.7
4.1
6.1
5.2
4.1
3.0
Residual head*, medium circle, heat source side (W10//B8/4//W35):
Heat pump
EcoTouch
DS
5008.5Ai
DS
5010.5Ai
DS
5012.5Ai
DS
5014.5Ai
DS
5017.5Ai
DS
5020.5Ai
DS
5023.5Ai
DS
5027.5Ai
Flow rate
T 4K
m³/h
1.4
1.7
2.2
2.5
3.2
3.5
4.1
4.6
Pump (class A)
25/1-7
25/1-7
25/1-7
25/1-7
25/1-8
25/1-8
25/1-8
25/1-8
Residual head
T 5K
mWS
6.1
5.8
4.7
4.2
5.6
5.0
3.9
2.9
* medium circle (15% Ethylen-Glykol and 85% water)
Summary of Contents for EcoTouch DS 5027 Ai
Page 50: ...Connection diagrams 2005 06 10 50 60 Copyright 2013 by WATERKOTTE GmbH Subject to changes...
Page 51: ...Connection diagrams 2005 06 10 51 60 Copyright 2013 by WATERKOTTE GmbH Subject to changes...
Page 52: ...Connection diagrams 2005 06 10 52 60 Copyright 2013 by WATERKOTTE GmbH Subject to changes...
Page 53: ...Connection diagrams 2005 06 10 53 60 Copyright 2013 by WATERKOTTE GmbH Subject to changes...
Page 54: ...Connection diagrams 2005 06 10 54 60 Copyright 2013 by WATERKOTTE GmbH Subject to changes...
Page 55: ...Connection diagrams 2005 06 10 55 60 Copyright 2013 by WATERKOTTE GmbH Subject to changes...
Page 59: ...Technical Data 2005 06 10 59 60 Copyright 2013 by WATERKOTTE GmbH Subject to changes...