Plan and MSR-equipment
MSR-
No.
Instrumentation
Component
PIC/1
Measurement of pressure readout in the controller dis-
play and control in the electrical switchboard.
Pressure transmitter ND
TIC/2
Measurement of temperature, readout in the controller
display and control in the electrical switchboard.
NTC 10K, gauge: suction gas overheat-
ing
TIC/3
Measurement of temperature, readout in the controller
display and control in the electrical switchboard.
NTC 10K, gauge: condenser OUT =
Heating flow
TIC/4
Measurement of temperature, readout in the controller
display and control in the electrical switchboard.
NTC 10K, gauge: condenser IN =
Heating return
PIC/5
Measurement of pressure, readout in the controller
display and control in the electrical switchboard.
Pressure transmitter HD
PZ+/6
Safety pressure relief valve.
Safety pressure switch
TIC/7
Measurement of temperature, readout in the controller
display and control in the electrical switchboard.
NTC 10K, gauge: heat source IN Vd
TIC/8
Measurement of temperature, readout in the controller
display and control in the electrical switchboard.1
NTC 10K, gauge: heat source OUT Vd