background image

30119-41      Rev. 1.6/02-07

9

MODEL TR28-2

INDICATOR - TOTALIZER - TRANSMITTER

 

SOLID STATE CONSTRUCTION 

 

CURRENT OUTPUT 

 

PULSE OUTPUT SIGNAL

 

ONE  PULSE PER TOTALIZER COUNT 

 

DIGITAL DISPLAYS

5

9

/

16

"

8

15

/

16

"

TR28-2 SIDE VIEW

NOTES:
The transmitter will drive up to a maximum of 600 ohms loop
resistance.

Wire Size Information:
The distance of the communication line from transmitter to the
device the 4-20mA will operate depends on the loop resistance, the
wire size, and the power supply.  Based on a 24V DC power supply
and 22 gauge wire, we recommend a maximum loop of 3,500 feet.

(not used)

4-20 mA Output

Left Pin Right Pin

Green (-) Red (+)

Sensor Wiring Input

Left Pin Right Pin
Red (+) Black (-)

Power

Power Supply

Maximum

 

Supply

Voltage

Resistance of

for Loop

Instruments in Loop

Variable

15.0VDC

150

Ω

Ω

Ω

Ω

Ω

Variable

18.0VDC

300

Ω

Ω

Ω

Ω

Ω

Variable

21.0VDC

450

Ω

Ω

Ω

Ω

Ω

 IN36-1(24V)

24.0VDC

600

Ω

Ω

Ω

Ω

Ω

Variable

27.0VDC

750

Ω

Ω

Ω

Ω

Ω

Variable

30.0VDC

900

Ω

Ω

Ω

Ω

Ω

SHIELD TO PLAIN EARTH
GROUND AT PANEL END

RED (+)  AND GREEN (-)
4-20 mA (LOOP POWERED)

BLACK (-) AND WHITE (+)
FOR PULSE OUTPUT
(ONE CONTACT PER
TOTALIZER COUNT)

Isolated Pulse

Output

Left Pin Right Pin

Black (-) White (+)

X

W

X

W

W

X

W

X

Summary of Contents for TR28-2

Page 1: ...MANUAL PARTS LIST FEATURING MODEL CN08 2 DIGITAL INDICATOR TOTALIZER ENCAPSULATED ELECTRONICS SOLID STATE CONSTRUCTION CURRENT OUTPUT SIGNAL PULSE OUTPUT SIGNAL SEALED HOUSING 3255 WEST STETSON AVENU...

Page 2: ...arantees or liabilities arising by law or otherwise Seller shall not incur any other obliga tions or liabilities or be liable to buyer or any customer of buyer for any anticipated or lost profits inci...

Page 3: ...TEMPERATURE Operation 32 to 160 F RANGE Storage 40 to 160 F Consultfactoryforspecialconstructionforother temperatures INPUT SIGNAL Type Voltage pulse Voltage Range 1 to 10V Minimum Frequency 0 125Hz M...

Page 4: ...e wiring connec tions must be made to the transmitter Connect the wire from the transmitter output cable 13 to the mA output terminal on the bottom of the unit The output is polarized Be sure terminal...

Page 5: ...24 VDC loop power to the Model TR28 2 is now on then use troubleshooting pro cedures 2 3 5 6 X XI and XII B If the meter indicator totalizer and remote in strument do not operate check the TR28 2 by...

Page 6: ...CHECK YOUR INSTRUMENT to be sure it is op erating properly by following the instrument service manual Check to be sure your instrument is operating correctly when a simulated signal is put into it WAR...

Page 7: ...sewhere Sometimes it is necessary to lay another line from the transmitter to instrument above ground to help prove the lines are at fault prior to pulling and replacing existing line Communications l...

Page 8: ...ER RESET WIRE IF DESIRED SEE IN16 DATA SHEET WHITE BLACK WHITE BLACK PULSE OUTPUT WIRING WHEN USED WITH AUXILIARY EQUIPMENT PULSE OUTPUT WIRING WHEN USED WITH MODEL IN16 MODEL TR28 2 MODEL TR28 2 Isol...

Page 9: ...size and the power supply Based on a 24V DC power supply and 22 gauge wire we recommend a maximum loop of 3 500 feet not used 4 20 mA Output Left Pin Right Pin Green Red Sensor Wiring Input Left Pin R...

Page 10: ...4 20 mA OUTPUT WIRED TO A MODEL IN48 12 CHART RECORDER SOLD BEFORE 05 93 250 OHM RESISTOR JUMPER RED GREEN AMMETER 4 20 mA NOTE Connections for checking transmitter power supply voltage 24 VDC Connect...

Page 11: ...R FROM RECORDER NOTE TRANSMITTER CABLE SHIELD TO GROUND JUMPER GREEN J2 PLUG 4 20 mA J11 PLUG TRANSMITTER POWER 24 VDC 4 20 mA Output Left Pin Right Pin Green Red TB 2 GREEN RED Isolated Pulse Output...

Page 12: ...8 1 4318 5 1 1551 17 4 4141 1 1 1115 10 10B 1 1551 18 3 1701 4 1 1711 5 No 1 2 3 4 5 6 8 9 10 11 12 13 14 Description Digital Indicator Totalizer Bonnet Assembly O ring Digital Indicator Totalizer Bon...

Page 13: ...30119 41 Rev 1 6 02 07 13 DIGITAL INDICATOR TOTALIZER TRANSMITTER MODEL TR28 2 FOR ELECTRONIC PROPELLER METERS...

Reviews: