background image

30119-41      Rev. 1.6/02-07

5

REPROGRAMMING:

  The bonnet can be lifted enough

to slide the base cup and digital transmitter out of the

bonnet, allowing access to the programming buttons.

(See Programming Guide, Literature #30110-17.)

3. SENSOR  ASSEMBLY

 in the meter can be  re-

placed by following the meter instruction manual.

4. BATTERY REPLACEMENT (#6):

  The 3 Volt

Lithium Battery is used as a backup to the 24 VDC loop

power.  In the event of a power loss, the battery will

continue to operate the rate and total functions of the

TR28-2.  The “low battery” indication will appear ap-

proximately 6 months prior to expiration.

A.

The bonnet (#1) can be lifted enough to ac-

cess the terminals connected to sensor input and trans-

mitter pulse/mA output.

B

.

Carefully disconnect the wires from the

transmitter.  The unit can then be turned over and the

battery can be accessed through the opening in the

bottom of the base cup.  Be sure to install the new

battery with the positive (+) and negative (-) terminals

positioned properly.

C.

Reconnect the wires to the transmitter.  (See

page 9.)

D.

Reinsert the TR28-2 (#4) into the bonnet as-

sembly (#1) with the 

top of dial aligned with the

hinge side of the bonnet

.

E.

Install the bonnet O-ring (#2) into bonnet

with a coating of silicone grease.

NOTE:  Batteries should be disposed of in an envi-

ronmentally sound manner.

IX. TROUBLESHOOTING 

the transmitter is necessary if it

is apparent that the instrument being controlled by the

transmitter is not receiving a proper signal from the

transmitter, and/or the totalizer or indicator-totalizer is

not functioning.  Before beginning, it is important to be

sure that the problem is with the transmitter.

The following checks should be made:

1)

Check to be sure that water is flowing through the

meter at flows above the minimum flow rate for the

given size meter.

2)

Check the instrument to be sure it has the required

power being supplied to it.

3)

Check the junction box to be sure the communica-

tion lines from the transmitter to the instrument are

making good contact and that the transmitter is wired

properly to the instrument.  (See wiring diagrams on

page 8, 10 or 11.)

1. THE TROUBLESHOOTING GUIDE 

is provided to

help isolate any problem that may occur with the trans-

mitter.  Follow the instructions and test procedures

listed for each problem.

NOTE

:

The meter assembly should be inspected

thoroughly to be sure it is operating properly and is not

the cause of the problem.  (Refer to your meter service

manual for instruction on inspection of the meter.)

A.

If the meter indicator-totalizer 

does

 work, but

the remote instrument 

does not

 operate (not receiving

proper signal), and if the 24 VDC loop power to the

Model TR28-2 is now on, then use troubleshooting pro-

cedures 2, 3, 5, 6, X, XI and XII.

B.

If the meter indicator-totalizer and remote in-

strument 

do not

 operate, check the TR28-2 by opening

and closing the lid twice.  If no response, then follow all

procedures.

2. WORKING AREA 

chosen for testing and inspec-

tion of the internal components should be clean to re-

duce the chance of dust or dirt particles being intro-

duced into the transmitter mechanism.

3. TR28-2 DIGITAL TRANSMITTER 

must be re-

moved from the mounting base (#10) to gain access to

the transmitter terminals and to check connections.

Remove the unit from the mounting base following in-

structions in section VIII.  Check the connection from

the sensor in the meter to the terminals in the bottom

of the TR28-2.  Check the connection from the pulse

and mA terminals on the TR28-2 to the instrument.

Make sure the connection is clean and tight, and that

the terminal is secure.

4. MOISTURE 

should not be apparent within the

transmitter bonnet (#1).  All O-rings should be inspected

for breaks or presence of foreign materials that allow

leakage to occur.  Check to be sure water is not coming

up through the meter head.  If water is coming up

through the meter head then the meter should be

checked.  (See meter service manual.)

5. TRANSMITTER COMMUNICATION LINES (#13)

should be checked to determine the current level flow-

ing in the loop.  The method of measurement is to insert

a multimeter into the 4-20 mA loop by disconnecting

one of the mA signal wires, clipping one side of multi-

meter to disconnected wire and connecting other end of

multi-meter to the lug or post from which the wire was

removed.

A. If no water is flowing

 through the meter,

the current level should be 4.0 mA.  The purpose of the

4.0 mA at no flow is to ensure that the loop is com-

plete.  If there is 4.0 mA in the loop when no water is

flowing, then the loop is intact.

B. If water is flowing

 through the meter, the

current level should be between 4 and 20 mA, depend-

ing on flow.

6. TR28-2 CIRCUIT 

should be checked to be sure it

is functioning properly.  The circuit may be checked as

follows:

A.

If the current level in the loop is 0.0 mA,

check the voltage between the mA terminals at the

transmitter.  It should be at the maximum power supply

level (± 1.0 VDC).

If there is no voltage present, then check the loop

voltage at its source.  If there is voltage at the voltage

source, then there is an opening in the loop.

If there is no voltage at the power supply, discon-

nect loop and check supply by itself.  If the voltage level

is still 0 VDC or very low (<10 VDC), replace power

supply.

B.

If the level of current is greater than 20 mA,

there are two possibilities.  The TR28-2 may be starting

to fail, but unless there has been some major damage

done to the unit (physical impact or voltage levels above

Summary of Contents for TR28-2

Page 1: ...MANUAL PARTS LIST FEATURING MODEL CN08 2 DIGITAL INDICATOR TOTALIZER ENCAPSULATED ELECTRONICS SOLID STATE CONSTRUCTION CURRENT OUTPUT SIGNAL PULSE OUTPUT SIGNAL SEALED HOUSING 3255 WEST STETSON AVENU...

Page 2: ...arantees or liabilities arising by law or otherwise Seller shall not incur any other obliga tions or liabilities or be liable to buyer or any customer of buyer for any anticipated or lost profits inci...

Page 3: ...TEMPERATURE Operation 32 to 160 F RANGE Storage 40 to 160 F Consultfactoryforspecialconstructionforother temperatures INPUT SIGNAL Type Voltage pulse Voltage Range 1 to 10V Minimum Frequency 0 125Hz M...

Page 4: ...e wiring connec tions must be made to the transmitter Connect the wire from the transmitter output cable 13 to the mA output terminal on the bottom of the unit The output is polarized Be sure terminal...

Page 5: ...24 VDC loop power to the Model TR28 2 is now on then use troubleshooting pro cedures 2 3 5 6 X XI and XII B If the meter indicator totalizer and remote in strument do not operate check the TR28 2 by...

Page 6: ...CHECK YOUR INSTRUMENT to be sure it is op erating properly by following the instrument service manual Check to be sure your instrument is operating correctly when a simulated signal is put into it WAR...

Page 7: ...sewhere Sometimes it is necessary to lay another line from the transmitter to instrument above ground to help prove the lines are at fault prior to pulling and replacing existing line Communications l...

Page 8: ...ER RESET WIRE IF DESIRED SEE IN16 DATA SHEET WHITE BLACK WHITE BLACK PULSE OUTPUT WIRING WHEN USED WITH AUXILIARY EQUIPMENT PULSE OUTPUT WIRING WHEN USED WITH MODEL IN16 MODEL TR28 2 MODEL TR28 2 Isol...

Page 9: ...size and the power supply Based on a 24V DC power supply and 22 gauge wire we recommend a maximum loop of 3 500 feet not used 4 20 mA Output Left Pin Right Pin Green Red Sensor Wiring Input Left Pin R...

Page 10: ...4 20 mA OUTPUT WIRED TO A MODEL IN48 12 CHART RECORDER SOLD BEFORE 05 93 250 OHM RESISTOR JUMPER RED GREEN AMMETER 4 20 mA NOTE Connections for checking transmitter power supply voltage 24 VDC Connect...

Page 11: ...R FROM RECORDER NOTE TRANSMITTER CABLE SHIELD TO GROUND JUMPER GREEN J2 PLUG 4 20 mA J11 PLUG TRANSMITTER POWER 24 VDC 4 20 mA Output Left Pin Right Pin Green Red TB 2 GREEN RED Isolated Pulse Output...

Page 12: ...8 1 4318 5 1 1551 17 4 4141 1 1 1115 10 10B 1 1551 18 3 1701 4 1 1711 5 No 1 2 3 4 5 6 8 9 10 11 12 13 14 Description Digital Indicator Totalizer Bonnet Assembly O ring Digital Indicator Totalizer Bon...

Page 13: ...30119 41 Rev 1 6 02 07 13 DIGITAL INDICATOR TOTALIZER TRANSMITTER MODEL TR28 2 FOR ELECTRONIC PROPELLER METERS...

Reviews: