TERMINALS
L
System Power 24 VAC (+)
LN
System Neutral (-)
RC
Remote Control
BT
Battery Test (+)
TG
Test Ground (-)
C1
Not Used
C2
Not Used
NC1
Not Used
NC2
Not Used
NO1
Not Used
NO2
Not Used
AC
24 VAC Out (+)
Power Failure: Terminal AC changes to 24 V square wave from battery/
inverter. Actuator responds to position of contact between WH#3 (Y)
and Terminal AC.
Operation:
On - Off Normal: Terminal L is connected to 24 VAC building power.
Terminal LN completes the circuit to BK. Actuator responds to opening
and closing of contact between WH# 3(Y) and Terminal AC.
VMS-35 WIRING DIAGRAM ON-OFF CONTROL
Power
24 VAC
HOT
Existing Jumper
L
LN RC LN TG BT
AC LN
NC1
C1 NO1
NC2
C2 NO2
(RECOMMENDED)
(RECOMMENDED)
OUTPUT TO
ACTUATOR A
OUTPUT TO
ACTUATOR B
(IF USED)
Actuator B
Actuator A
1.
The VMS-35 can power one (1) or two (2) actuators.
2.
Energize 24 VAC before connecting red lead to battery.
3.
Also read actuator wiring and setup instructions.
N
O
TES
VMS-35
OR#5(U) WH#3(Y) RD#2(+) BK#1(-)
OR#5(U) WH#3(Y) RD#2(+) BK#1(-)
ADDENDUM B