3
HVAC_BAC_ELECTRIC_IOM_RevCa_0219
OVERVIEW
ADAPTION POWER
The actuators feature a native
2-10 Vdc Control Signal.
Installation of the KR500
Resistor Kit converts the
Control Signal input to 4-20
mAdc. When using 4-20 mA
input, terminate the 500 ohm
resistor from the KR500 resistor
kit between the White and
Black actuator wires. When
using the VMS-35, this can be
easily done between the NO1
and LN terminals for Actuator
1 and between the NO2 and LN
terminals for Actuator 2.
A single wire brings a 2-10 Vdc
Feedback Signal. The Feedback
Signal is not available using
4-20 mAdc.
The Rotation Switch can be
adjusted to set the direction
the Control Signal opens and
closes the valve (and Loss
of Signal direction in some
actuators) in the field without
actuator removal.
Adaption (Auto-Calibration
- green LED), a combined
Adaption/ Power button to
reset and relearn the valve
stroke as well as indicate the
actuator is powered. When the
Button is pressed, the actuator
will drive one full cycle to
its mechanical end stops OR
the valves mechanical seats.
Upon completion of this cycle
the actuators working range
(Control Signal, Feedback
Signal and running time) will
be adjusted to the actual
stroke of the actuator.
Status (yellow LED) to confirm
communication.
DANGER
PRESS THE MANUAL OVERRIDE
BUTTON IN FIRMLY WHILE
OPERATING THE MANUAL
OVERRIDE. FAILURE TO DO SO
WHILE THE ACTUATOR IS POWERED
OR BEING DRIVEN TO THE POWER
FAILURE DIRECTION CAN CAUSE
SERIOUS PERSONAL INJURY AND
DAMAGE THE ACTUATOR.
!
Manual Override is possible by turning off the power, pressing the Manual Override button
and rotating the supplied Allen key in the Hex Override Socket.
(E024, E029, E030)
(E025, E026)
E024
E029
E030
E025
E026
E024
E029
E030
E025
E026
•
The override button can
lock in place for NON-
CAPACITOR E024, E029
and E030 actuators.
Press the button down
and into the actuator
to lock. The OVERRIDE
BUTTON will remain
down and will need to
be pressed to return
to its original position.
•
The button must be
continuously pressed
completely down
throughout travel for
E025 AND E026 actuators
with CAPACITORS.
WARNING: Do not force or turn the HEX OVERRIDE SOCKET when the OVERRIDE BUTTON is not
pressed. Doing so may cause damage to the actuator gears.
Engage the manual override:
To raise the actuator stem turn the Allen key counter-clockwise.