background image

Preliminar

y

3

                                            ILEA-A/B_IOM_NoRev_1118

USAGE AS PER SPECIFICATION

•  ARIA Series actuators are exclusively designed to be used as 

electric valve actuators for rising stem globe control valves. 

They are meant to be mounted on Warren Controls, control 

valves in order to run their motors.

•  Any other use is considered to be non-compliant and the 

manufacturer cannot be held liable for any damage resulting 

from it.

•  The actuators can only be used within the limits laid out in the 

data sheets, catalogues and other documents. Otherwise, the 

manufacturer cannot be held liable for any resulting damage.

•  Usage as per specification includes the observance of the 

operating, service and maintenance conditions laid down by 

the manufacturer.

•  Read this document in its entirety as special precautions 

need to be taken before mounting and adjusting the actuator 

as well as servicing!

•  The actuators may only be used, serviced and repaired by 

personnel that is familiar with them and informed about 

potential hazards. The specific regulations for the prevention 

of accidents have to be observed.

• Damages caused by unauthorized modifications carried 

out on the actuators are excluded from the manufacturer’s 

liability.

•  Supply voltage may only be switched on after the proper 

closure of the main cover or terminal box.

ILEA SERIES BASIC SPECIFICATIONS

Spring-Fail
ARIA

 Stroke Speed

12 Secs/In., (2 mm/sec.), Fixed. 

Spring-Fail Speed: 2.3 mm/sec.

What happens under the condition of Loss 

of Power, under voltage or over voltage.

Actuator engages Spring Fail, to Open or Close, Depending on model.

What happens under the condition of 

Loss of Control Signal.

Actuator engages Spring Fail, to Open or Close, Depending on model. With control by 

binary inputs, actuator stops in position when event occurs.

MAX Thrust: 455 Lbf (2kN)

MAX Stroke: 1.38 In. (35mm)

Manual Override (electric): via 2 push buttons when powered

Power Supply: 24 VAC/DC, optionally wide range PS (100-240 VAC)

Motor protection: Electronic motor current monitoring with safety cut-off

Duty cycle as per IEC 60034-1,8: S2 30 min/ S4 1200c/h-50% ED

Permitted ambient temperature: -4ºF to 140ºF (-20ºC to +60ºC)

Internal fault monitoring: Thrust, Control Signal, Temperature, Power Supply

Binary control: 24-230- VAC for ON/OFF service

Control Signal and Feedback: 0-20 mA, 4-20 mA, 0-10 V, 2-10 V selectable, plus split range

Mounting Position: Any position, except cover pointing downwards

Conduit entries: 2 pcs. M 20 x 1.5 /1 pc. M 16 x15

Enclosure Rating. to EN 60529: IP67

Fuse - HV Power Supply: 2 AMP, 5 x 20 mm, 250 VAC, Slow Blow

POWER CONSUMPTION

25 WATTS, MAX CURRENT

1.8 A at 24 VAC / DC
0.36 A at 115 VAC
0.18 A at 230 VAC

OPERATING CONDITIONS AND INSTALLATION POSITION

•   Standard actuators may be operated at ambient temperatures according to the 

ARIA Series basic specifications.

•   Operating modes correspond to IEC 60034-1, 8: S2 for short cycle and S4 for 

modulating operation.

•   For protection against moisture and dust, the enclosure rating is IP65 according 

to EN 60529.

•   When installing the actuators, leave enough space to allow cover removal.
•   The actuator can be installed vertically or horizontally or any position in between. 

The actuator must not be installed with the cover pointing downwards.

Outdoor usage: 

 When using the actuators in environments 

with high temperature fluctuations or high humidity, we 

recommend using the optional heating resistor. IP67

Installation 
positions

Summary of Contents for ARIA Series

Page 1: ...allation 3 Removing Closing the Cover 4 Wiring Diagram 4 High Voltage Power Supply 4 Electric Supply 5 Mount Add Pos Switches Mech Relays 5 DIP Switch Functions Settings 6 Manual Operation 6 Actuator...

Page 2: ...em are connected as well Based on a brushless DC motor BLDC the generated torque is transmitted via a multi stage spur gear onto a spindle nut The spindle nut transmits the input torque into an axial...

Page 3: ...dition of Loss of Control Signal Actuator engages Spring Fail to Open or Close Depending on model With control by binary inputs actuator stops in position when event occurs MAX Thrust 455 Lbf 2kN MAX...

Page 4: ...ce PC Communication Commissioning Galvanically isolated 1 kV Process Sensor Option Position switch potential free contact Electric supply for 1 phase AC DC REMOVING CLOSING THE COVER Open Loosen the s...

Page 5: ...equirement of the actuator The yellow green colored cables may only be used for connecting to earth When you insert the cable through the drive cable connector ensure that the max bending radius for t...

Page 6: ...Preliminary 6 2600 Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com POSITION SWITCH SET UP OPTIONAL FAULT RELAY DESCRIPTION...

Page 7: ...Preliminary 7 ILEA A B_IOM_NoRev_1118 DEFAULT PARAMETERS SOFTWARE SET UP...

Page 8: ...Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com ACTUATOR PARTS IDENTIFICATION Pillar Clamping Screws for Spring Pack Valve Stem Locking Nut Yoke Lock Nut Coupling Coupling Nut...

Page 9: ...Preliminary 9 ILEA A B_IOM_NoRev_1118 ACTUATOR REMOVAL REPLACEMENT INSTRUCTIONS...

Page 10: ...IONING Only available if at least one of the cut offs is set to be by force torque or by position automatically 1 Press the commissioning button for 3 sec 2 Commissioning in progress Green LED is flas...

Page 11: ...Preliminary 11 ILEA A B_IOM_NoRev_1118...

Page 12: ...meters see instrucions AMS PSCS 2 Connect process sensor x x Actuator position does not correspond to set value input A non linear valve curve has been parameterised Verify parameterised characteristi...

Page 13: ...has been passed over Valve seat worn or defective Check the valve seat x x Actuator supply voltage too low 1 Improper wiring of the mains supply 2 Jitter in supply voltage 3 Too low supply voltage fro...

Page 14: ...Preliminary 14 2600 Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com...

Page 15: ...Preliminary 15 ILEA A B_IOM_NoRev_1118...

Page 16: ...2600 EMRICK BLVD BETHLEHEM PA 18020 USA 800 922 0085 WWW WARRENCONTROLS COM DEPENDABLE RUGGED PRECISION CONTROL VALVES AND ACCESSORIES ILEA A B_IOM_NoRev_1018 92500136 No Rev Preliminary...