  Faults within the actuator’s 

environment 

Probable reasons 

Possible remedy 

  

  

  

  

  

    Actuator drives into a preset 

position 

1) Signal is applied to the 

binary fail‐safe input 

2) Supply voltage failure on 

actuators with optional 

PSCP 

1) Disconnect the signal  

2) Check supply voltage 

  

  

  

  

  

  

x  Set‐value disconnected or outside 

the parameterized range 

1) Set‐value not connected 

2) Wrong polarity of set‐

value 

3) set‐value signal outside 

parameter range, please 

check 

1) Apply set‐value 

2) Check the set‐value 

polarity 

3) Check the set‐value range 

  

  

  

  

  

   Stored end position could not be 

reached 

Loose or dirty valve seat 

Check the valve seat 

  

  

  

  

 

  

   Stored end position has been 

passed over 

Valve seat worn or defective  Check the valve seat 

  

  

  

  

  

   Actuator supply voltage too low 

1) Improper wiring of the 

mains supply 

2) Jitter in supply voltage 

3) Too low supply voltage 

from PSEP (with optional 

PSEP) 

1) Check mains wiring 

2) Check supply voltage ‐> 

see datasheet 

3) Contact PS service team 

  

  

  

  

  

  

  

   Faults within the actuator  

Probable reasons 

Possible remedy 

  

  

  

  

  

   Actuator has reached lifetime limit  Wear and/ or running time   Contact PS service team 

  

  

  

  

 

  

   Faulty electronics or invalid 

parameters 

1) Supply voltage 

interrupted during 

commissioning 

2) Defective electronic 

component 

1) Reload parameters (‐> see 

manual AMS‐PSCS), then 

repeat commissioning 

2) Contact PS service team 

  

  

  

  

  

   Critical or maximum temperature 

reached 

1) Too high numbers of 

starts  

2) Ambient temperature too 

high 

1) Check application and its 

adjustment  

2) Check ambient 

temperature and try to 

reduce it ‐> see relevant data 

sheet 

  

  

  

  

  

  

x  Mechanical fault in the actuator  

Defective mechanical part 

Contact PS service team 

 
 

 

TRACING FAULTS CHARTS (A/B ONLY)

Summary of Contents for ARIA Series

Page 1: ...allation 3 Removing Closing the Cover 4 Wiring Diagram 4 High Voltage Power Supply 4 Electric Supply 5 Mount Add Pos Switches Mech Relays 5 DIP Switch Functions Settings 6 Manual Operation 6 Actuator...

Page 2: ...em are connected as well Based on a brushless DC motor BLDC the generated torque is transmitted via a multi stage spur gear onto a spindle nut The spindle nut transmits the input torque into an axial...

Page 3: ...dition of Loss of Control Signal Actuator engages Spring Fail to Open or Close Depending on model With control by binary inputs actuator stops in position when event occurs MAX Thrust 455 Lbf 2kN MAX...

Page 4: ...ce PC Communication Commissioning Galvanically isolated 1 kV Process Sensor Option Position switch potential free contact Electric supply for 1 phase AC DC REMOVING CLOSING THE COVER Open Loosen the s...

Page 5: ...equirement of the actuator The yellow green colored cables may only be used for connecting to earth When you insert the cable through the drive cable connector ensure that the max bending radius for t...

Page 6: ...Preliminary 6 2600 Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com POSITION SWITCH SET UP OPTIONAL FAULT RELAY DESCRIPTION...

Page 7: ...Preliminary 7 ILEA A B_IOM_NoRev_1118 DEFAULT PARAMETERS SOFTWARE SET UP...

Page 8: ...Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com ACTUATOR PARTS IDENTIFICATION Pillar Clamping Screws for Spring Pack Valve Stem Locking Nut Yoke Lock Nut Coupling Coupling Nut...

Page 9: ...Preliminary 9 ILEA A B_IOM_NoRev_1118 ACTUATOR REMOVAL REPLACEMENT INSTRUCTIONS...

Page 10: ...IONING Only available if at least one of the cut offs is set to be by force torque or by position automatically 1 Press the commissioning button for 3 sec 2 Commissioning in progress Green LED is flas...

Page 11: ...Preliminary 11 ILEA A B_IOM_NoRev_1118...

Page 12: ...meters see instrucions AMS PSCS 2 Connect process sensor x x Actuator position does not correspond to set value input A non linear valve curve has been parameterised Verify parameterised characteristi...

Page 13: ...has been passed over Valve seat worn or defective Check the valve seat x x Actuator supply voltage too low 1 Improper wiring of the mains supply 2 Jitter in supply voltage 3 Too low supply voltage fro...

Page 14: ...Preliminary 14 2600 Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com...

Page 15: ...Preliminary 15 ILEA A B_IOM_NoRev_1118...

Page 16: ...2600 EMRICK BLVD BETHLEHEM PA 18020 USA 800 922 0085 WWW WARRENCONTROLS COM DEPENDABLE RUGGED PRECISION CONTROL VALVES AND ACCESSORIES ILEA A B_IOM_NoRev_1018 92500136 No Rev Preliminary...

Reviews: