SYMBOLS AND SAFETY

Please ensure that the detailed operating instructions and the chapter on “Safety” in particular have been read and 

understood by all personnel involved in the installation, start-up, operation, maintenance and repair of the actuators.

Beware of mechanical hazards due to electrically powered actuator components! With the actuator powered 

electrically, operating the unit holds the danger of crushing your finger!

Caution! During the installation of the actuator on the valve, the unit must not be powered electrically. Disconnect 

voltage from the actuator before maintenance and adjustment work. 

During adjustment work, the actuator must be operated by means of the handwheel only. Do not operate electrically!

DO NOT FULLY EXTEND. 

FUNCTION

The ARIA Series actuators are designed as Spring-Fail-Safe upon 
Loss of- Power, or Loss-of-Signal. The actuator is mounted onto 
the control valve via pillars and mounting base and attached via 
a yoke locknut. The actuator stem and valve stem are connected 
as well.

Based on a brushless DC motor (BLDC) the generated torque is 
transmitted via a multi-stage spur gear onto a spindle nut. The 

spindle nut transmits the input torque into an axial thrust force 
via a spindle. The linear stroke is transmitted to the valve spindle 
by a coupling piece.

The stroke is measured and controlled by a linear 12 Bit Hall 
sensor. In case of mains power loss, the stroke movement is 
in OPEN or CLOSE direction by spring force. Electrical wiring is 
terminated at a terminal block under the actuator cover.

DANGER SIGNS

 Caution!

 There is a general risk of damage related to health and/or properties.

 Danger!

 Electrical voltages are present that may lead to death. Life threatening risks 

 

may occur due to electrical voltages!

 Danger! 

This sign warns of hazards posing a risk to health. Ignoring these instructions can lead to injuries.

Other notes

•  The motor surface temperature may rise when maintaining, inspecting and repairing the actuator immediately after 

operation. There is a danger of burning the skin!

•  Always consult the relevant operating instructions when mounting ARIA accessories or operating the actuator with 

ARIA accessories.

•  Connections for signal in- and output are double isolated from circuits that can be under dangerous voltage

Summary of Contents for ARIA Series

Page 1: ...allation 3 Removing Closing the Cover 4 Wiring Diagram 4 High Voltage Power Supply 4 Electric Supply 5 Mount Add Pos Switches Mech Relays 5 DIP Switch Functions Settings 6 Manual Operation 6 Actuator...

Page 2: ...em are connected as well Based on a brushless DC motor BLDC the generated torque is transmitted via a multi stage spur gear onto a spindle nut The spindle nut transmits the input torque into an axial...

Page 3: ...dition of Loss of Control Signal Actuator engages Spring Fail to Open or Close Depending on model With control by binary inputs actuator stops in position when event occurs MAX Thrust 455 Lbf 2kN MAX...

Page 4: ...ce PC Communication Commissioning Galvanically isolated 1 kV Process Sensor Option Position switch potential free contact Electric supply for 1 phase AC DC REMOVING CLOSING THE COVER Open Loosen the s...

Page 5: ...equirement of the actuator The yellow green colored cables may only be used for connecting to earth When you insert the cable through the drive cable connector ensure that the max bending radius for t...

Page 6: ...Preliminary 6 2600 Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com POSITION SWITCH SET UP OPTIONAL FAULT RELAY DESCRIPTION...

Page 7: ...Preliminary 7 ILEA A B_IOM_NoRev_1118 DEFAULT PARAMETERS SOFTWARE SET UP...

Page 8: ...Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com ACTUATOR PARTS IDENTIFICATION Pillar Clamping Screws for Spring Pack Valve Stem Locking Nut Yoke Lock Nut Coupling Coupling Nut...

Page 9: ...Preliminary 9 ILEA A B_IOM_NoRev_1118 ACTUATOR REMOVAL REPLACEMENT INSTRUCTIONS...

Page 10: ...IONING Only available if at least one of the cut offs is set to be by force torque or by position automatically 1 Press the commissioning button for 3 sec 2 Commissioning in progress Green LED is flas...

Page 11: ...Preliminary 11 ILEA A B_IOM_NoRev_1118...

Page 12: ...meters see instrucions AMS PSCS 2 Connect process sensor x x Actuator position does not correspond to set value input A non linear valve curve has been parameterised Verify parameterised characteristi...

Page 13: ...has been passed over Valve seat worn or defective Check the valve seat x x Actuator supply voltage too low 1 Improper wiring of the mains supply 2 Jitter in supply voltage 3 Too low supply voltage fro...

Page 14: ...Preliminary 14 2600 Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com...