To access advances setting, 

PRESS

 and 

HOLD

      and      simultaneously for 5 seconds.

PRESS

 

SET

 

to navigate through the different advanced settings. Use      or      to adjust the setting. 

PRESS OK

 to

exit advanced settings

Display Function

Range

Default

CL

Display temperature calibration

-4 °C - + 4 °C

0

bL

Backlight

1 = (OFF) 2 = (ON) 3 = (Always ON)

2

AF

Sensor selection

A = Air sensor       

F  =  Floor  sensor     AF = Air with 

floor limit**

AF

AH

Set maximum settable temperature 

for floor sensor (F), air sensor (A) 

and air sensor with floor limit (AF)

Floor Sensor 

(F) + 18°C - + 35°C

Air Sensor/Air Sensor with Floor Limit 

(A/AF) + 18°C - + 45°C

F = (45°C)

A = (35°C)

AF = (35°C)

FL

Minimum floor 

temperature limit

Floor Sensor (F) + 5°C - + 20°C

10°C

FH

Maximum floor 

temperature limit 

Floor Sensor (F) + 25°C - + 50°C

50°C

PS

Weekly schedule day selection

3 = (1-5 Block, 1 + 1)       7 = 7 Days

3

CS

No. of programs per day

P4 = 4 Programs per day / P6 = 6 Programs per day

P4

CF

Select °Celsius / °Fahrenheit

C = °Celsius / F = °Fahrenheit

°C

CO

Set 24hr

 /

12hr Clock

24h / 12h

24h

LD

Set heating load* 

HH = (16 - 12 A), H = (11 - 8 A), L (

7 A)

H

SE

Sensor Selection

100 = 100K / 10 = 10K sensor 

100

To reset advanced settings to factory default 

PRESS

 and 

HOLD

      for 3 seconds when the thermostat is idle and the 

heating schedule mode is displayed,       . 

ConF

 will flash, 

PRESS OK

 to accept.

* Failing to set the Heating Load correctly will reduce the accuracy of the thermostats air temperature reading

** To view current floor temperature when the thermostat is set to AF (Air with floor limit), 

PRESS

 and 

HOLD

      for 3 

seconds 

Advanced Settings

Troubleshooting

Code Fault

Action

E1

Floor sensor short circuit in type F or AF

Check the sensor resistance and replace if it is damaged. Expected 

resistance: 100kΩ at 25°C, 125.5kΩ at 20°C, 157.4kΩ at 15°C

E2

Floor sensor not installed or broken in 

type AF

Check the sen

sor resistance and replace if it is damaged. Expected 

resistance: 100kΩ at 25°C, 125.5kΩ at 20°C, 157.4kΩ at 15°C

E3

Air sensor short circuit

Exchange device or operate using floor sensor only

E4

Air sensor damaged

Exchange device or operate using floor sensor only

E5

Wrong floor sensor installed

Remove floor sensor and install a 100K or 10K floor sensor

2

Open Window Function - 

The

 

Warmup One features open window function which detects when there is a sudden drop 

in temperature (1.5°C or more within 3 minutes) when a window is opened and will switch your heating off saving 

you energy. The heating will reactivate if the temperature increases again (1.5°C in 30 minutes). 

PRESS

 any button to 

return to heating schedule mode.

Warmup - IM - One - v1.0 2018-07-31.indd   2

31/07/2018   10:58:30

Summary of Contents for One

Page 1: ...he Warmup One requires a permanent power supply from a 30mA RCD protected circuit in accordance with the current edition of the Wiring Regulations The thermostat and its power supply should be isolated from the mains supply throughout the installation process Ensure that wires are fully inserted into the terminals with no bare wire visible and secured Any free strands should be trimmed as they cou...

Page 2: ...ating schedule mode is displayed ConF will flash PRESS OK to accept Failing to set the Heating Load correctly will reduce the accuracy of the thermostats air temperature reading To view current floor temperature when the thermostat is set to AF Air with floor limit PRESS and HOLD for 3 seconds Advanced Settings Troubleshooting Code Fault Action E1 Floor sensor short circuit in type F or AF Check t...

Page 3: ... Schedule Setting a Heating Schedule allows you to set comfort temperatures at set times throughout the day The thermostat can bet set so that MON FRI 1 5 is programmed as a block with SAT 6 and SUN 7 programmed individually Alternatively the thermostat can set so that you program each day individually see advanced settings on how to switch between schedule settings Typically when setting a 6 peri...

Page 4: ...o heating schedule mode PRESS OK Setting a Temporary Override Warmup warrants this product to be free from defects in the workmanship or materials under normal use and service for a period of 1 year from the date of purchase by the consumer If at any time during the warranty period the product is determined to be defective Warmup shall repair or replace it at Warmup s discretion If the product is ...

Page 5: ...att de sitter ordentligt åtdragna Felaktig installation kan leda till kortslutning och brand Matningsspänning 100 240 V AC 50 60 Hz Modell ONESTAT IP Klass IP21 Maxbelastning 16 A 3840 W Installationsdjup Min 35mm Dimentioner H W D 81 x 81 x 25 mm Från vägg Sensor Luft och Golv Kompabilitet eUFH Sensortyp 2 5m NTC 100K Kan utökas till max 50 m Er P Klass I Issoleringsklass II Standard EN60730 1 EN...

Page 6: ... för klocka visas ConF kommer blinka TRYCK OK för att acceptera Felaktig installning av termostatens belastning kan leda till felaktig temperaturdata För att se aktuellt temperaturvärde när termostaten är inställd på AF Luft och golv Tyck och HÅLL inne i 3 sekunder Avancerade inställningar Felsökning KOD Fel Action E1 Golvsensor kortsluten F eller AF Testa sensor och byt om skadad Mätvärde enligt ...

Page 7: ...rläge Schemalagt läge Schemalagt läge låter dig välja olika temperaturer under dagen Termostaten kan ställas in till MÅN FRE 1 5 är programmerat som ett block med Lör 6 och Sön 7 programmerat som ett speparat Alternativt kan varje dag programeras separat se Avancerade inställningar Standardinställningen vid ett 6 periodsschema kommer period 1 3 coh 5 vara påslagen värme och period 2 4 och 6 kommer...

Page 8: ...tt vanliga schema vid nästa periodstart för att avbryta avikande läge välj schemalagt läge och TRYCK OK Inställningar för tillfällig avvikelse Warmup garanterar att denna produkt är fri från defekter i utförande eller funktion under normal användning under en period av 1 år från inköpsdatum Om produkten på något sätt under garantiperioden är defekt ska Warmup reparera eller byta ut det Om produkte...

Reviews: