background image

57

warmhaus.com

Error Code

Description of the Error

Malfunction

Probable Cause

Solution(s)

E 43

O p e n t h e r m 
communication error

Boiler does not work, E43 
error code flashing on the 
screen after 1 minute of 
communucation error

Opentherm line 
disconnected

1-) Remove energy from boiler and re energised E43 will be removed 
and boiler & buttons will get back to funcitional
2-) Replace the room unit batteries with the fresh ones and reset from 
room unit 
3-) Check cabeling between boiler and room thermostat unit and re 
connect if any disconnection, if connection set up succesfully then 
connection symbol will be activated on the screen 
4-) Call for authorised service to re connect openterm connection 

rE 44

Cumulated intermittent 
ignition without reaching 
burner ignition. 

Boiler does not work, E44 
error code flashing on the 
screen

"> Intermittent contacts on 
harness
> Hammer effect on water 
net 
> Too many request from 
in shotr time from out side 
room units or thermosad 
bridge etc. "

1-) Call For service
2-) Check for domestic heating water net this problem generally 
generated by installation root cause water hammer effect. To eliminate 
this adjust P26=2 or 3 on TsP Menu
3-) Check intermittent contacts on harness carefully
4-) Check room unit or thermostad bridge againt too many request 
in short time

E 62

Calibration request

Boiler does not work, E62 
error code flashing on the 
screen 

"> Calibration not done
> Replacing board but not 
service key from the board 
dismantled
> Service key damaged or 
disconnected
> Updating Software
 ( probable )"

1-) Call For service
2-) Check TsP default values before calibration specially P15, P31, P32, 
P33
2-) Perform Auto Calibration.

Attention: Only authorised service must perform Au-To 

calibration

E 72

Delta T heating at ignition 
not occurred

Boiler does not work, E72 
error code flashing on the 
screen 

> FLOW OR RETURN 
Sensor not on position

1-) Call for authorised service at first
2-) Check RETURN and FLOW sensor on position.

E 74

Second CH temperature 
Probe faulty

Boiler does not work, E74 
error code flashing on the 
screen 

> FLOW and LIMIT Sensor ( 
double NTC ) faulty

1-) Call for authorised service at first
2-) Check CH temperature probe ressistance (double CH NTC probe 
is used as high temperature limit device) if its out of tolerance replace 
double NTC
3-) Check cabeling and connectors between double NTC and board
4-) Reset & Restart boiler

E 77

Absolute current values 
reached

Boiler does not work, E77 
error code flashing on the 
screen 

> Gas inlet pressure
> Aging or rust on the 
electrode
> Recirculation on fluegas 
path
> Blokage on flue or wrong 
flue
> Electrode position
> Cabeling disconnections
> Combustion calibration
> Electronic board
> Gas valve failiure

1-) Call for authorised service at first
2-) Check gas supply pressure must be 20-17 mbar. Gas pressure must 
be in between on this values while boiler on operational
3-) Check wrong flue OR flue gas blockage 
4-) Check recirculation ( flue gas leak ) from flue gas path to fresh air 
side, check flue gas sealings specially
5-) Check any problems on the ionisation electrode, (like condensation, 
rust etc.), and control poistioning of the electrode, if electrode poistion 
wrong calibrate electrode.
6-) Check if the heat exchanger coils clogged or not
7-) Check for condensation on the cabling AND/OR on board
8-) Check earth connection between board and electrode
9-) Check electrode cabeling between board and electrode
10-) Check combustion CO2 or O2 values on HI and LO mode at sweeper 
mode. 
11-) Perform Auto Calibration.
12-) If fault still persists Replace board, but use original service key 
from the board dismantled to keep original parameters and calibration 
points. If original service key not used aslo adjust P15 releated to the 
default value of boiler power and perform Au-To calibration. 
13-) If not successfull replace gas valve, and Perform Au-To calibration. 

Attention: Only authorised service must perform Au-To calibration

E 78

Max regulation current 
value reached

Boiler does not work, E78 
error code flashing on the 
screen 

> Gas inlet pressure
> Aging or rust on the 
electrode
> Recirculation on fluegas 
path
> Blokage on flue or wrong 
flue
> Electrode position
> Cabeling disconnections
> Combustion calibration
> Electronic board
> Gas valve failiure

1-) Call for authorised service at first
2-) Check gas supply pressure must be 20-17 mbar. Gas pressure must 
be in between on this values while boiler on operational
3-) Check wrong flue OR flue gas blockage 
4-) Check recirculation ( flue gas leak ) from flue gas path to fresh air 
side, check flue gas sealings specially
5-) Check any problems on the ionisation electrode, (like condensation, 
rust etc.), and control poistioning of the electrode, if electrode poistion 
wrong calibrate electrode.
6-) Check if the heat exchanger coils clogged or not
7-) Check for condensation on the cabling AND/OR on board
8-) Check earth connection between board and electrode
9-) Check electrode cabeling between board and electrode
10-) Check combustion CO2 or O2 values on HI and LO mode at sweeper 
mode. 
11-) Perform Auto Calibration.
12-) If fault still persists Replace board, but use original service key 
from the board dismantled to keep original parameters and calibration 
points. If original service key not used aslo adjust P15 releated to the 
default value of boiler power and perform Au-To calibration. 
13-) if not successfull replace valve, and Perform Au-To calibration. 

Attention: Only authorised service must perform Au-To calibration

Summary of Contents for EWA 20

Page 1: ...CONDENSING COMBI BOILER INSTALLATION MANUAL EWA 20 EWA 24...

Page 2: ...EWA 20 EWA 24...

Page 3: ...n Case of Using Bottled Gas 9 Filling the siphon for Condensation Line 10 Installation at Partially Protected Exteriors 10 Electrical Connections 10 Optional Controls Room Thermostat Outside Sensor an...

Page 4: ...4 warmhaus com...

Page 5: ...ilable BE FR YES II 2H3B P Natural Gas 20 mbar G20 Available AT CH CY CZ DK EE FI GR IT LT NO RO SE SI SK YES II 2E3B P Natural Gas 20 mbar G20 Available DE YES II 2ELL3B P Natural Gas 20 mbar G20 Ava...

Page 6: ...6 warmhaus com...

Page 7: ...Figure 2 User s Guide Figure 5 Exhaust gas flue set 471 1000 GAS G3 4 G3 4 G3 4 80 mm 65 mm 65 mm 64 mm 725 mm 592 mm 422 mm G1 2 G1 2 75 mm 73 mm 110 m m 114 mm OPTIONAL Ewa Priwa ERP Priwa ERP Plus...

Page 8: ...r semi full brick wall according to installation scheme and with connection screws and not to be used for other purposes In case of using different materials for installation combi shall be out of the...

Page 9: ...1 2 7 In Case of Using LPG Tank LPG use is recommended for heat requirements over 24 kW New LPG stock tanks may contain settled gas residues nitrogen however that pauperises the mixture assigned to t...

Page 10: ...able to use gas and water connection pipes for earthing WARMHAUS A cannot be held as responsible for any damages and losses on individuals or commodities arising from failing to provide earth connecti...

Page 11: ...nsor is activated when connected as independent from the used room thermostat typology and functions as common with room thermostats The relation between installation input temperature and exterior we...

Page 12: ...0 600021 WT RF03 Large Screen Modulated Weekly Program Scheduled Wireless room thermostat Product code 153 11 660 600022 150 cm Min 30 cm Room thermostat shall be mounted 1 25 to 1 5 m above the groun...

Page 13: ...d in the hot tap water Hydrophore should be used if required Prior to filling the radiator installation it must be flushed and all wastes must be cleaned Warning In order to prevent invalidity of devi...

Page 14: ...mum 3 storey buildings Drainage and Ventilation Pipe Min 19 mm Water Air proof insulation Figure 2 26 Connection of condensate Drainage Pipe to External Soil Vent Stack Connection of Condensate Draina...

Page 15: ...thorized service appointment request Gas opening approval certificate should be taken from the local gas company for your gas line Combi electricity connection should be made via 2 or 3 Amps fuse Figu...

Page 16: ...o be used in exhaust gas installation of hermetic combi should be original Warmhaus flue sets and they should be used by considering measurements and restrictions given in installation instructions In...

Page 17: ...ontent 10 00 tolerance 0 5 0 5 maximum allowable draught and maximum allowable pressure difference between combustion air inlet and flue gas outlet including wind pressures 120 Pa characteristics and...

Page 18: ...temperature for dimensioning the common duct system shall be declared as 25 C c the combustion product mass flow rate at maximum heat input shall be specified for every connection point the terminal...

Page 19: ...H C R A I J K I L S B T U Likely flue positions requiring a flue terminal guard Figure 32 Environmental locations of flue Terminal Position with Minimum Distance mm A1 Directly below an opening air br...

Page 20: ...tion hatch edge must not be fitted more than 1 5 meters away from a flue joint Inspection hatches should be fitted at every change of direction Flue Data 60 100mm Concentric flue systems information W...

Page 21: ...ceed 10 m with single elbow horizontally Also this total length reduces by 1 m with every 90 elbows or two 45 elbows Maximum 3 pieces of 90 elbow can be used a Standard Flue Set Elbow 90 b Flue Extens...

Page 22: ...es Flue Data WARNING Warmhaus flue pipe technical specification Vertical Termination Maximum length 11 meters including the bend or adaptor connected directly to the boiler Effective flue length for t...

Page 23: ...al flue set installation application Implementation L1 0 3 m L2 0 5 m 45 elbow equivalent length L3 2 0 m L4 0 5 m 45 elbow equivalent length L5 1 0 m L6 1 5 m L Total 6 3 m 6 3 m Lmax 11 m Correct in...

Page 24: ...ension of 140 mm see Table 1 It must not be sited above the flue pipe The flue and air pipes must extend by at least 40 mm from the wall surface Condensing boiler emit a visible plume of water vapour...

Page 25: ...0 Condensing Flue Extension L 1000 mm 15311660600015 White 60 100 Condensing Flue Extension L 2000 mm 15311660600016 White 60 100 Condensing 45 Elbow 15311660600017 White 60 100 Condensing 90 Elbow L...

Page 26: ...0 mm 80 mm L 500 mm 153 11 660 600091 80 Condensing Twin Flue Extension Pipe L 1000 mm 80 mm L 1000 mm 153 11 660 600092 80 Condensing Twin Flue Extension Pipe L 2000 mm 80 mm L 2000 mm 153 11 660 600...

Page 27: ...n products will not cause a nuisance and that the terminal will not obstruct the passageway 3 If a terminal is less than 2 metres above a balcony above ground or above a at roof to which people have a...

Page 28: ...NTC 4 Check cabling and connectors between double NTC and board 5 Reset Restart boiler E 06 No ignition Boiler does not work E06 error code flashing on the screen Gas supply failure 1 RESET boiler che...

Page 29: ...ault Boiler does not work E12 error code flashing on the screen Domestic heating water temperature sensor in storage tank faulty 1 Check intermittent contacts or open contacts on harness carefully 2 C...

Page 30: ...ed 2 Check the root cause of Error code to solve 3 If fault still persists call for authorised service E 37 Low voltage anomaly Boiler does not work E37 error code flashing on the screen Low voltage 1...

Page 31: ...onnections Combustion calibration Electronic board Gas valve failiure 1 Call for authorised service at first 2 Check gas supply pressure must be 20 17 mbar Gas pressure must be in between on this valu...

Page 32: ...ulation flue gas leak from flue gas path to fresh air side check flue gas sealings specially 5 Check any problems on the ionisation electrode like condensation rust etc and control poistioning of the...

Page 33: ...e electrode 5 Check for condensation on the cabling AND OR on board 6 Check earth connection between board and electrode 7 Check electrode cabeling between board and electrode 8 Check combustion CO2 o...

Page 34: ...sed service must perform Au To calibration E 96 Flue or air suction way blockage Boiler does not work E96 error code flashing on the screen Blokage on flue Blokage on air suction path 1 Call for autho...

Page 35: ...omestic Hot Water Circuit Water Heating Energy Efficiency Class A A A Water Heating Declared Load Profile XL L XL Water Heating Energy Efficiency 85 81 84 Gas Consumption at Maximum m h 2 47 2 83 0 73...

Page 36: ...Heating Energy Efficiency s 91 92 92 Useful efficiency at rated heat output and high temperature regime 2 4 87 60 87 57 87 57 Useful efficiency at 30 of rated heat output and low temperature regime 1...

Page 37: ...arefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold subject to our...

Page 38: ...EWA 20 EWA 24 CONDENSING COMBI BOILER INSTALL ATION MANUALEwa Installation Service Manual Code 15011606000140 Revision Date R00 12 2021...

Reviews: