21
warmhaus.com
Total equivalent length
≤
10 m
a (90° Elbow) + b + c (90° Elbow) + d
≤
10 m
L2
a- Standard Flue Set Elbow (90°)
b- Flue Extension Pipe
c- Additional 90° Elbow = 1 m
d- Standard Flue Set Pipe
Total equivalent length
≤
10 m
a (90° Elbow) + b + c (45° Elbow) + d + e (45° Elbow) + f
≤
10 m
L1
L2
a
b c
d
e
L3
f
Total length of hermetic flue set should not exceed 10 m with single elbow
horizontally. Also, this total length reduces by 1 m with every 90° elbows or
two 45° elbows. Maximum 3 pieces of 90° elbow can be used.
a- Standard Flue Set Elbow (90°)
b- Flue Extension Pipe (L1)
c- Additional 45° Elbow = 0,5 m
d- Standard Flue Set Pipe (L2)
e- Additional 45° Elbow = 0,5 m
f- Standard Flue Set Pipe (L3)
Figure 37.
Two 90° elbow sample flue installations
Figure 38
Single 90° and two 45° elbow sample flue installations
One 90° elbow and two 45° elbow
sample flue installations.
0041_01.W201215
0042_01.W201215