1.2.10. Installation at Partially Protected Exteriors

Installation instructions:

 This combi can be installed in partially protected 

exteriors. Partially protected place means that the combi is located at places 
without direct exposure to atmospheric factors and precipitations (rain, 
snow, etc.).

Frost protection:

 Combi device is equipped with a system that prevents 

frost by automatically activating the pump and boiler when the internal 
water is lower than 5°C.
Frost protection function only depends on below given conditions:
-  If the combi is correctly connected to gas and electrical sources;
-  If the combi is supplied from gas and electricity sources (if the main switch 

is open) in a fixed way;

-  If the Combi is not in failure situation due to lack of ignition;
-  In order to maintain circulation of installation water, installation valves and 

radiator valves under the combi must be open.

Under these conditions, the combi is protected against frost up to -5°C 
environment temperature.

Lowest Temperature -5°C.

 In case the combi is installed in an environment 

with a temperature lower than -5°C, and gas supply is interrupted or passed 
into failure due to failing to make ignition, Frost Prevention System shall not 
be activated and frost/failure shall occur in the device. Following instructions 
should be followed for preventing the risk of frost:

- Heating circuit, into antifreeze (special heating devices) a good brand of
antifreeze manufacturer's instructions are followed carefully so as it deems
necessary for the rate and the minimum temperature is desired to be stored in
the heater frost protection with the matter.

Materials used for manufacturing the combi are resistant against glycol and 
propylene based anti-frost liquids. Follow warnings of supplier company 
regarding their lives and possible disposals.

Frost / icing protection of the combi is guaranteed only under these 

conditions:

Damages arising from failing to follow above mentioned issues and 
interruption of electricity supply shall be excluded from validity of the 
warranty.

In case the combi device is installed at places with temperature lower than 
0°C (both for tap water and radiator purposes) both radiator installation and 
tap water pipes must be insulated.

1.2.11. Electrical Connections

Electrical safety of combi shall be realized if completely connected to an 
effective earthing installation that follows safety instructions in force. No 
earthing shall be made from the neutral line on the socket for places not 
having earthing! It is dangerous and unacceptable to use gas and water 
connection pipes for earthing.

WARMHAUS A.Ş. cannot be held as responsible for any damages and 

losses on individuals or commodities arising from failing to provide 

earth connection of the combi and not being provided by a competent 

electrician in accordance with directives and standards in force.

Also, ensure that the electricity installation complies with the maximum power 
to be supplied as indicated in technical specifications label on the combi. Combi 
is given with "X" type socketless special power source cables. "Warmhaus combi 
has an IPX5D protection level. Power supply cable should be connected by relying 
on earth connection and L-N poles in a 230 V +%10; -%15 50Hz grid, high voltage 
category 3rd class multiple pole disconnector should be envisaged on the same 
grid. Apply out Authorized Warmhaus Service for replacement of the cable. 

1.2.9. Filling the siphon for Condensation Line

After the wall hanging operation of condensing combi, electrical connections, 
radiator lines, hot tap water connections and condensation water drainage 
line are completed, condensation siphon should be filled with water (Figure 
9). 

Condensation line drain line impermeability should be maintained. 
However, prior to installation of the flue bend of the siphon in the 
combi, discharge 1 litre water to the internal flue against the 

possibility of flue gas leakage possibility at first start. Thus, waste gas leakage 
possibility shall be prevented with the water available in siphon.

Slope of condensation water hose and line must be always towards down.

Attentions For Condensate Drain:

FAILURE TO INSTALL THE CONDENSATE DISCHARGE PIPEWORK 

CORRECTLY WILL AFFECT THE RELIABLE OPERATION OF THE BOILER

1. Ensure the discharge of condensate complies with any national or local

regulations in force.

2. The discharge pipe should be run in a proprietary drain pipe material e.g.

PVC, PVC-U, ABS, PVC-C or PP.

3. Metal pipework is NOT suitable for use in condensate discharge systems.
4. Any condensate discharge pipework external to the building (or in an

unheated part of it e.g. garage) must be insulated to protect against frost.

5. In all cases discharge pipe must be installed to aid disposal of the

condensate. To reduce the risk of condensate being trapped, as few bends 
and fittings as possible should be used.

6. When discharging condensate into a soil stack or waste pipe the effects

of existing plumbing must be considered. If soil pipes or waste pipes are
subjected to internal pressure fluctuations when WC's are flushed or sinks 
emptied then back-pressure may force water out of the boiler trap and
cause appliance lockout.

7. Condensate outlet shall not be modified or blocked always be downwards.

Figure 9 

Filling the condensation siphon

1 liter

Summary of Contents for EWA 20

Page 1: ...CONDENSING COMBI BOILER INSTALLATION MANUAL EWA 20 EWA 24...

Page 2: ...EWA 20 EWA 24...

Page 3: ...n Case of Using Bottled Gas 9 Filling the siphon for Condensation Line 10 Installation at Partially Protected Exteriors 10 Electrical Connections 10 Optional Controls Room Thermostat Outside Sensor an...

Page 4: ...4 warmhaus com...

Page 5: ...ilable BE FR YES II 2H3B P Natural Gas 20 mbar G20 Available AT CH CY CZ DK EE FI GR IT LT NO RO SE SI SK YES II 2E3B P Natural Gas 20 mbar G20 Available DE YES II 2ELL3B P Natural Gas 20 mbar G20 Ava...

Page 6: ...6 warmhaus com...

Page 7: ...Figure 2 User s Guide Figure 5 Exhaust gas flue set 471 1000 GAS G3 4 G3 4 G3 4 80 mm 65 mm 65 mm 64 mm 725 mm 592 mm 422 mm G1 2 G1 2 75 mm 73 mm 110 m m 114 mm OPTIONAL Ewa Priwa ERP Priwa ERP Plus...

Page 8: ...r semi full brick wall according to installation scheme and with connection screws and not to be used for other purposes In case of using different materials for installation combi shall be out of the...

Page 9: ...1 2 7 In Case of Using LPG Tank LPG use is recommended for heat requirements over 24 kW New LPG stock tanks may contain settled gas residues nitrogen however that pauperises the mixture assigned to t...

Page 10: ...able to use gas and water connection pipes for earthing WARMHAUS A cannot be held as responsible for any damages and losses on individuals or commodities arising from failing to provide earth connecti...

Page 11: ...nsor is activated when connected as independent from the used room thermostat typology and functions as common with room thermostats The relation between installation input temperature and exterior we...

Page 12: ...0 600021 WT RF03 Large Screen Modulated Weekly Program Scheduled Wireless room thermostat Product code 153 11 660 600022 150 cm Min 30 cm Room thermostat shall be mounted 1 25 to 1 5 m above the groun...

Page 13: ...d in the hot tap water Hydrophore should be used if required Prior to filling the radiator installation it must be flushed and all wastes must be cleaned Warning In order to prevent invalidity of devi...

Page 14: ...mum 3 storey buildings Drainage and Ventilation Pipe Min 19 mm Water Air proof insulation Figure 2 26 Connection of condensate Drainage Pipe to External Soil Vent Stack Connection of Condensate Draina...

Page 15: ...thorized service appointment request Gas opening approval certificate should be taken from the local gas company for your gas line Combi electricity connection should be made via 2 or 3 Amps fuse Figu...

Page 16: ...o be used in exhaust gas installation of hermetic combi should be original Warmhaus flue sets and they should be used by considering measurements and restrictions given in installation instructions In...

Page 17: ...ontent 10 00 tolerance 0 5 0 5 maximum allowable draught and maximum allowable pressure difference between combustion air inlet and flue gas outlet including wind pressures 120 Pa characteristics and...

Page 18: ...temperature for dimensioning the common duct system shall be declared as 25 C c the combustion product mass flow rate at maximum heat input shall be specified for every connection point the terminal...

Page 19: ...H C R A I J K I L S B T U Likely flue positions requiring a flue terminal guard Figure 32 Environmental locations of flue Terminal Position with Minimum Distance mm A1 Directly below an opening air br...

Page 20: ...tion hatch edge must not be fitted more than 1 5 meters away from a flue joint Inspection hatches should be fitted at every change of direction Flue Data 60 100mm Concentric flue systems information W...

Page 21: ...ceed 10 m with single elbow horizontally Also this total length reduces by 1 m with every 90 elbows or two 45 elbows Maximum 3 pieces of 90 elbow can be used a Standard Flue Set Elbow 90 b Flue Extens...

Page 22: ...es Flue Data WARNING Warmhaus flue pipe technical specification Vertical Termination Maximum length 11 meters including the bend or adaptor connected directly to the boiler Effective flue length for t...

Page 23: ...al flue set installation application Implementation L1 0 3 m L2 0 5 m 45 elbow equivalent length L3 2 0 m L4 0 5 m 45 elbow equivalent length L5 1 0 m L6 1 5 m L Total 6 3 m 6 3 m Lmax 11 m Correct in...

Page 24: ...ension of 140 mm see Table 1 It must not be sited above the flue pipe The flue and air pipes must extend by at least 40 mm from the wall surface Condensing boiler emit a visible plume of water vapour...

Page 25: ...0 Condensing Flue Extension L 1000 mm 15311660600015 White 60 100 Condensing Flue Extension L 2000 mm 15311660600016 White 60 100 Condensing 45 Elbow 15311660600017 White 60 100 Condensing 90 Elbow L...

Page 26: ...0 mm 80 mm L 500 mm 153 11 660 600091 80 Condensing Twin Flue Extension Pipe L 1000 mm 80 mm L 1000 mm 153 11 660 600092 80 Condensing Twin Flue Extension Pipe L 2000 mm 80 mm L 2000 mm 153 11 660 600...

Page 27: ...n products will not cause a nuisance and that the terminal will not obstruct the passageway 3 If a terminal is less than 2 metres above a balcony above ground or above a at roof to which people have a...

Page 28: ...NTC 4 Check cabling and connectors between double NTC and board 5 Reset Restart boiler E 06 No ignition Boiler does not work E06 error code flashing on the screen Gas supply failure 1 RESET boiler che...

Page 29: ...ault Boiler does not work E12 error code flashing on the screen Domestic heating water temperature sensor in storage tank faulty 1 Check intermittent contacts or open contacts on harness carefully 2 C...

Page 30: ...ed 2 Check the root cause of Error code to solve 3 If fault still persists call for authorised service E 37 Low voltage anomaly Boiler does not work E37 error code flashing on the screen Low voltage 1...

Page 31: ...onnections Combustion calibration Electronic board Gas valve failiure 1 Call for authorised service at first 2 Check gas supply pressure must be 20 17 mbar Gas pressure must be in between on this valu...

Page 32: ...ulation flue gas leak from flue gas path to fresh air side check flue gas sealings specially 5 Check any problems on the ionisation electrode like condensation rust etc and control poistioning of the...

Page 33: ...e electrode 5 Check for condensation on the cabling AND OR on board 6 Check earth connection between board and electrode 7 Check electrode cabeling between board and electrode 8 Check combustion CO2 o...

Page 34: ...sed service must perform Au To calibration E 96 Flue or air suction way blockage Boiler does not work E96 error code flashing on the screen Blokage on flue Blokage on air suction path 1 Call for autho...

Page 35: ...omestic Hot Water Circuit Water Heating Energy Efficiency Class A A A Water Heating Declared Load Profile XL L XL Water Heating Energy Efficiency 85 81 84 Gas Consumption at Maximum m h 2 47 2 83 0 73...

Page 36: ...Heating Energy Efficiency s 91 92 92 Useful efficiency at rated heat output and high temperature regime 2 4 87 60 87 57 87 57 Useful efficiency at 30 of rated heat output and low temperature regime 1...

Page 37: ...arefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold subject to our...

Page 38: ...EWA 20 EWA 24 CONDENSING COMBI BOILER INSTALL ATION MANUALEwa Installation Service Manual Code 15011606000140 Revision Date R00 12 2021...

Reviews: