1.6. INSTALLATION WITH VERTICAL FLUE SETS
(Ø60/100 MM)
Your Warmhaus boiler can also be installed with a vertical flue system that
can terminate on both flat and pitched roofs, vertical flue installations must
not exceed 11 m in total.
Apply a suitable lubricant to the sealing joints before connecting any flue
products and ensure the vertical flue terminal is installed level without a
slope.
The vertical flue terminal can be fitted to both flat and pitched surfaces.
Flue Data
WARNING
Warmhaus flue pipe technical specification:
Vertical Termination:
• Maximum length = 11 meters including the bend or adaptor connected
directly to the boiler.
• Effective flue length for the following:
Elbow
Equivalent To Straight Length
45 Degree
0.5 meter
90 Degree
1.0 meter
Ø60/100mm, L max = 11m
A
Figure 40
Waste gas vertical outlet chimney set and Pitched Roof Outlet Tile part
installation for Roof
INFORMATION:
The vertical flue terminal can be fitted to both flat
and
pitched
surfaces.
Figure 41
Waste gas vertical outlet flue set Roof insulation and flue transition part
0043_01.W210420
0044_0
1.W210
70
7
Figure 39
Vertical flue set installation
0045_00.D181122