background image

 

2

1  GENERAL INFORMATION 

1.1 Warnings 

In  order  to  qualify  for  the  product  guarantee  the  equipment 

MUST

  be  correctly 

commissioned

 as described herein and the 

guarantee registration section

 at the back of 

this manual 

completed and returned

Failure to commission and register the product may invalidate ALL guarantees. 

This  equipment  must  only  be  installed  and  commissioned  by  professionally  qualified 
personnel in accordance with current laws and standards and in line with the manufacturer’s 
instructions.  It is recommended that the system is installed by a competent installer such as 
those  registered  under  the  Microgeneration  Certification  Scheme  (MCS)  in  the  United 
Kingdom or with Sustainable Energy Ireland (SEI) in the Republic of Ireland. 

The installation must comply with the requirements of: 

the Building Regulations 

current IEE Wiring Regulations or ETCI rules for electrical installations 

Where no specific instructions are given, reference should be made to the relevant European 
Standards. 

This  equipment  must  be  used  solely  for  the  purpose  for  which  it  was  designed  and 
manufactured – indirect heating of stored water (e.g. domestic hot water production). 

Any  other  use  is  deemed  improper  and  as  such  dangerous.   The manufacturer  accepts  no 
liability  for  damage  or  injury  to  persons  or  animals  caused  as  a  result  of  errors  in  the 
installation  and/or  use  of  the  equipment,  or  through  non-compliance  with  current  local  and 
national standards and/or the manufacturer’s instructions. 

This equipment is only suitable for use in a sealed solar thermal system filled with the system 
fluid  supplied  or  specifically  recommended  by  the  manufacturer.    The  means  of  heating 
domestic  hot  water  (DHW),  a  swimming  pool  or  other  medium  must  be  via  a  suitable  heat 
exchanger, for example the coil of a DHW storage cylinder. 

This  instruction  manual  forms  an  integral  and  essential  part  of  the  equipment  and  must  be 
kept  in  a  safe  place,  available  for  future  reference.    This  manual,  along  with  the 
commissioning and service records and proof of purchase, must be left with the end user. 

 

It is essential that the heat pipe tubes are protected from overheating prior to installation. 

NEVER leave uninstalled heat pipe tubes exposed to the sun. 

Only  unpack  and  install  the  heat  pipe  tubes  after  the  rest  of  the  system  had  been  flushed, 
filled and pressure tested and the system is ready to be brought into operation i.e. the DHW 
storage cylinder is in use or the swimming pool has been filled. 

If for any long periods there will be no heat load on the system (e.g. property unoccupied or 
swimming  pool  emptied)  the  solar  collector  must  either  be  covered  or  the  heat  pipe  tubes 
removed.  If installing the collector onto a new-build property, DO NOT install the tubes until 
the property is, or is about to become, occupied. 

 

Due  to  the  high  temperatures  that  may  be  generated  by  a  solar  installation  it  is 
recommended that a mixing valve be fitted to the hot water outlet from a domestic hot water 
storage  cylinder  in  order  to  limit  the  domestic  hot  water  temperature.  A  setting  of  60ºC  is 
recommended. 

Summary of Contents for Solar SHP20

Page 1: ...structions Maintenance Instructions Guarantee Registration Solar Thermal Systems European Solar Keymark Approved Products covered by this manual Solar SHP20 SHP30 Heat pipe vacuum tube collectors and...

Page 2: ......

Page 3: ...Connect pump station pipework 16 3 5 Electrical Installation 17 3 5 1 Mount controller 17 3 5 2 Connect external wiring centre 17 3 5 3 Connect back up heat source 18 4 Commissioning 19 4 1 System Fil...

Page 4: ...l standards and or the manufacturer s instructions This equipment is only suitable for use in a sealed solar thermal system filled with the system fluid supplied or specifically recommended by the man...

Page 5: ...turer s instructions The equipment can be regarded as electrically safe when connected to an effective earthing system installed in accordance with the requirements of current regulations This fundame...

Page 6: ...50 x 2100 x 154 Weight empty kg 66 5 95 0 Fluid volume litres 1 2 1 7 Operating data Rated flow rate per collector litres min 2 0 3 0 Max flow rate per collector litres min 20 Max operating pressure b...

Page 7: ...se thermal losses similar to a vacuum flask Vacuum Tube High efficiency twin wall glass tube with 360 0 advanced Al N Al coated absorber surface applied by Magnetron Sutter CVD for maximum absorption...

Page 8: ...ssure Relief Valve Flow from Collector Return to Collector Flow to Solar Coil Return from Solar Coil Filling Point Circulating Pump Flow Adjuster Flow Indicator Pressure Gauge Flow Temperature Gauge R...

Page 9: ...ine Pump Station Pressure Relief Discharge Solar Expansion Vessel Motorised Valve if required Drain Cock at lowest point DHW Storage Cylinder Solar Coil Boiler Coil if applicable T3 T2 T1 T1 T2 T3 Sol...

Page 10: ...to 30m 15mm 1 x SEV18 up to 40m 22mm 1 x SEV18 up to 75m 22mm 2 x SEV18 50 up to 10m 15mm 1 x SEV18 up to 45m 22mm 2 x SEV18 Table 2 Pipework and expansion vessel sizing NOTE The total length of pipe...

Page 11: ...9 2 5 Collector Pressure Drop Figure 6 SHP20 collector pressure drop Figure 7 SHP30 collector pressure drop...

Page 12: ...east South west East West North east North west North 30 0 Recommended 4 3 loss 15 loss 27 loss 32 loss 45 0 1 8 loss 7 1 loss 20 loss 36 loss 40 loss 600 7 8 loss 14 loss 28 loss 44 loss 53 loss Dat...

Page 13: ...racket spacing is within the guidelines below As much as is possible space each set of brackets equally either side of each collector centreline In some instances depending on the tile design it may b...

Page 14: ...lied with the manifold to the lower end of the support frame and secure in place by tightening the clamps Ensure the clamps either side of the bottom rail face inwards towards it and that the edges of...

Page 15: ...on kit Solar SHPX Provide effective lightening protection by connecting a suitable conductor to either the flow or return connection of EACH collector installed Connect the pre insulated flexible hose...

Page 16: ...tube manifold installations respectively 3 3 1 Install slate roof brackets Using suitable fasteners not supplied fix the brackets to the most convenient rafters ensuring the bracket spacing is within...

Page 17: ...described in Section 3 2 3 bolting the brackets to the underside of the support frame rails using the same bolts that secure the manifold and bottom rail to the rails 3 3 3 Connect manifold pipework...

Page 18: ...o A must be the flow from the collector i e the end of the collector with fitted with the temperature sensor pocket Connect the pipework running from the solar coil of the DHW storage cylinder or swim...

Page 19: ...wiring centre via a fused spur isolator 3 5 2 Connect external wiring centre Specify an appropriate 5 wire motorised valve not supplied and connect it as shown Connect the high limit thermostat of the...

Page 20: ...stat not supplied If in doubt consult the cylinder manufacturer Only if connecting to an open vented cylinder can the back up heat source be connected directly to the system controller without a motor...

Page 21: ...sary release air by depressing the valve centre pin or top up with a foot pump 4 1 2 Calculate system volume Calculate the system volume referring to the cylinder manufacturer s instructions for the v...

Page 22: ...the circulating pump by accessing the HND Menu and setting HND1 to On Ensure that any motorised valve is activated and that the pump on the pump station is turning Bleed any air from the pump using th...

Page 23: ...d of the valve by hand Ensure the valve closes when released and that the flow of fluid ceases 4 3 Sensor Installation Referring to the Solar System Controller instruction booklet install and secure t...

Page 24: ...rame and manifold correctly installed as per Section 3 2 3 insert the heat exchanger end of the tube into the manifold Support the bottom end of the tube with your hand then slide on the tube end supp...

Page 25: ...ster Turn the flow adjuster to its mid position F which gives the maximum flow rate Read the flow rate from the flow indicator The reading is taken from the bottom edge of the float body Is the readin...

Page 26: ...e pressurised and bled using Warmflow Solar Fluid SF and an appropriate filling station 5 2 2 Check fluid health CAUTION The fluid may be EXTREMELY HOT Draw off a small amount of fluid via the bleed p...

Page 27: ...s in the solar circuit at all joints and valve seals 6 Colour check of the heat transfer medium 7 Acidity check of the heat transfer medium pH only if discoloured 8 Frost protection level of the heat...

Page 28: ...tent persons in accordance with the manufacturer s instructions and all relevant regulations and codes of practice in force at the time i each service record being completed and proof of purchase and...

Page 29: ...27 7 INSTALLATION NOTES Please use this section to record any important notes relevant to the installation which may be required for future reference...

Page 30: ...0869 WARMFLOW Customer Care Centre UK 028 9262 1515 ROI 048 9262 1515 Email service warmflow co uk THIS MANUAL IS ACCURATE AT THE DATE OF PRINTING E OE BUT MAY BE SUPERSEDED AND SHOULD BE DISREGARDED...

Page 31: ...ansion vessel bladder pressure checked prior to system filling tick Bladder pressure bar 10 System flushed then filled with Warmflow Solar Fluid tick 11 System flushed of all air filling station run f...

Page 32: ...ow using one of the 3 methods below By Post Using the prepaid envelope or otherwise to Warmflow Engineering Co Ltd Appliance Registration Department Lissue Industrial Estate Moira Road Lisburn BT28 2R...

Reviews: